background image

To connect a five-wire system (C, W, G, RC, RH, Y) to the 
thermostat: 

1.  Remove the orange jumper wire. 

2.  Connect the Y wire to the Y terminal on the thermostat. This 

connects the cooler compressor. 

3.  Connect the RH wire to the RH terminal on the thermostat. 

This connects the heater power. 

4.  Connect the RC wire to the RC terminal on the thermostat. 

This connects the cooling power. 

5.  Connect the W wire to the W terminal on the thermostat. This 

connects the heater control line. 

6.  Connect the G wire to the G terminal on the thermostat. This 

connects the fan.  

Your system is now connected to the thermostat. 

Figure 7: Five-wire connections 

C

RC

Thermostat

RH

W

Y

G

Cool power

Heat power

Heat

Cool
comp

Fan

HVAC system

RC

RH

W

Y

G

Remove

jumper
wire

C

 

Batteries 

The IS-ZW-TSTAT-100 requires three AA Alkaline batteries. 
Batteries are used for backup in case of power loss. We do not 
recommend the batteries as the primary source of power. 

To install the batteries: 

1.  Press the Heat/Cool Mode button to Off and press the Fan 

button to Auto. 

2.  Remove the bottom cover section to access the battery 

compartment. 

3.  Install three AA Alkaline batteries according to the polarity 

noted in the battery compartment. (Do not use rechargeable 
batteries.) 

4.  Replace the bottom cover. 

Replace the batteries when the red Low Battery LED indicator 
blinks or once a year. 

Caution: 

The thermostat will go “off” if the batteries die. This could 

expose your house to unexpected heat or cold. 

Testing 

Follow these procedures to verify you have correctly installed the 
thermostat (see Figure 1 on page 1). 

To check the fan (if you connected the G wire-fan relay): 

1.  Press the Fan button to On. 

2.  Verify that air is blowing from the system.  

3.  Return the Fan button to the Auto selection for normal 

operation. 

To check heat mode: 

1.  Press the Heat/Cool Mode button to Heat. 

2.  Press the + button to raise the target temperature to 90

°

F. 

Allow the system 2 minutes to respond. 

3.  Verify that heat is blowing from the system. 

4.  Return the Heat/Cool Mode button to Off.  

Leave off for 4 minutes before checking the cool mode. 

To check cool mode: 

Note: 

Do not operate AC if the outside temperature is below 65

°

F. 

1.  Press the Heat/Cool Mode button to Cool. 

2.  Press the blue (-) button to lower the cool target temperature 

to 50

°

F.  

Allow the system 5 minutes to respond. 

3.  Verify that cool air is blowing from the system. 

4.  Return the Heat/Cool Mode button to Off. 

If you have electric heat, locate the Gas/Elec switch. Move the 
selector jumper to the Elec position (see Figure 1 on page 1). 

Calibration 

The IS-ZW-TSTAT-100 thermostat comes from the factory 
calibrated to 

±

 1

°

 of actual temperature. If you want the 

thermostat to display the same temperature as another 
thermostat in the home, you can adjust its calibration. 

To change the calibration: 

1.  Remove the top cover section. 

2.  Locate the Calibration switch and slide it to the On position. 

The current calibration factor is (

±

) of the IS-ZW-TSTAT-100 

will appear in the LCD display.  

3.  Push the Up or Down arrows until the desired calibration 

factor is reached. 

4.  Slide the Calibration switch to the Off position. The new 

calibrated temperature will be displayed on the LCD.  

5.  Replace the top cover section. 

Reset 

The Reset button (located under the top cover) defaults all 
programming to target temperatures (heat 70

°

F, cool 75

°

F). 

4 of 6 

 

P/N 1069534 • REV A • ISS 17MAR10 

Summary of Contents for IS-ZW-TSTAT-100

Page 1: ...sic Thermostat Temp up button Temp down button Temperature display Heat Cool mode button Fan button Gas Elec switch Reset Calibrate F C Z Wave mate Terminals Installation Caution To avoid electrical shock and to prevent damage to the furnace air conditioner and thermostat disconnect the power supply before beginning work You can do this at the circuit breaker or at the HVAC system Note Verify the ...

Page 2: ...ide the wall You can wind them around a pencil to keep them from falling see Figure 2 below Make sure the wires do not fall back inside the wall You can wind them around a pencil to keep them from falling see Figure 2 below 6 Loosen all screws on the old thermostat and remove it from the wall 6 Loosen all screws on the old thermostat and remove it from the wall Figure 2 Label wires Figure 2 Label ...

Page 3: ...nnected to the thermostat Figure 4 Two wire connections C RC Thermostat RH W Y G Heat power Heat HVACsystem W jumper wire C R To connect a three wire system C W RH or R G to the thermostat 1 Connect the R or RH wire to the RH terminal on the thermostat This connects the heater power 2 Connect the W wire to the W terminal on the thermostat This connects the heater control line 3 Connect the G wire ...

Page 4: ...eck the fan if you connected the G wire fan relay 1 Press the Fan button to On 2 Verify that air is blowing from the system 3 Return the Fan button to the Auto selection for normal operation To check heat mode 1 Press the Heat Cool Mode button to Heat 2 Press the button to raise the target temperature to 90 F Allow the system 2 minutes to respond 3 Verify that heat is blowing from the system 4 Ret...

Page 5: ...mostat make sure the wires go through both holes and tighten them down 6 If the AC fails to turn on or blow warm air then the problem is with the AC system Specifications Voltage 24 VAC supplied via the C wire Backup batteries Three AA Alkaline batteries Duracell Energizer do not use rechargeable batteries Dimensions W H D 5 5 3 5 1 5 in 140 89 38 mm Operating environment Temperature Relative humi...

Page 6: ...6 of 6 P N 1069534 REV A ISS 17MAR10 ...

Reviews: