(*) By running these commands, an interactive menu is launched – follow the on-screen instructions.
The menu also provide a complete on-line help section.
NOTE
: When using the local serial connection, make sure that the terminal emulation is set to VT-100,
otherwise the interactive menu may not be rendered correctly.
Caution!
Some of these commands (particularly
upscontrol
and
upsconfig
) may inject commands
and/or alter the UPS configuration with consequences on the UPS operation that may affect the load.
Make sure you fully understand the effect on the UPS and on the load before injecting any of these
commands. Make sure that it is safe to perform the desired operation for both the UPS and the load.
2.2.11
Rccmd
command group
The
rccmd
command group allows to configure the RCCMD Server embedded in the SNMP/Web
adapter.
Command Sub-command Parameters
Description
showrccmd
Shows the current RCCMD Server
configuration
Enable/disable Network Shutdown function
on|off
on
Network Shutdown enabled
o
ff
Network Shutdown disabled)
add
Add an RCCMD Client
[ip]
IP-address of the trap target
[port]
Port on which the client is listening
[cond]
Shutdown condition:
aXX
after XX minutes on battery
bXX
at XX min remain batt time
[ip]
[port]
[cond]
rccmd
Send an RCCMD test message to a specific
RCCMD client
[num]
test
[row]
RCCMD client reference
Delete an RCCMD Client
[row]
RCCMD client reference
[num]
del
Modifications reserved
Page 24/58
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc
Operating Manual
SNMP/Web Adapter