OPM_GTU_TWR_1K0_3K0_XUS_V015
19
DE GT Series: User manual rev date 8-11- 04
Digital Energy
™
GT Series
g
GT Model
1000T UL
1500T UL 2000T UL
3000T UL
Capacity
1kVA/800W
1.5kVA/ 1200 W
2kVA/1600W
3kVA/2400W
Rated Voltage
100V, 110V, 120V
Voltage Range
80V~138V (full load); 65V ~80V (70% load)
Frequency
50Hz / 60Hz (± 4.8 Hz)
Input
Power Factor
≥
0.97
Voltage
100V, 110V, 120V
Frequency
50Hz / 60Hz
Voltage Regulation
± 2%
Frequency Accuracy
± 0.05 Hz
Wave Form
pure sine wave
Transient Response
± 8% (10%
∼
90% linear load)
THD (linear load)
≤
3%
≤
3%
≤
4%
THD (computer load)
≤
6%
Overload Capacity
105%~125% for 3mins; 125%~150% for 30secs; >150% for 1sec
Crest Factor
3:1
Output
Efficiency (AC-A C)
≥
87%
Outlet
Receptacles
NEMA TYPE
Battery Voltage
36V
72V
72V
Battery Type (Lead acid)
12V/7Ah
12V/7Ah
12V/9A h
Back-up Time
(Typical)
5mins
Battery
Recharge Time
4~6 hours after complete discharge to recover 90%
Transfer
Time
Transfer Time
zero
LED Status
On- line / Bypass / On- battery / Overload / Battery Low / Fault
Battery Replace / Battery Level / Load Level
LED
Alarm
buzzer
DB9
RS232/dry contact
Interface
SNMP Slot
internal
Noise (At 1 Meter)
40dB(A)
42dB(A)
45dB(A)
Operating
Temper ature
0~40°C (32~104°F)
Environment
Humidity
0%~90% (non-condensing)
Safety
UL/cUL
EMC
FCC Class A (2, 3kVA) /B (1kVA)
CISPR PUB 22 Class B; TUV/EMC; CE (1kVA)
CISPR PUB 22 Class A (2, 3kVA)
Safety
Approval
Lightning
IEEE 62.41 Category A
Battery Start
yes
Extended Battery
Bank
yes (optional for longer runtime)
Others
Long Time Model
yes (optional)
Dimensions
(W
×
D
×
H)
140x366x242 mm
5.5x14.4x9.5 inch
140x425x373mm
5.5x16.7x14.7 inch
Appearance
Weight
15 kg
33 lbs
30 kg
66 lbs
30 kg
66 lbs
8 - Specifications