GE Digital Energy

 

ML Series

g

 

 

 

 

 

 

5.1 General 

 

The UPS is virtually maintenance free: take care of proper environmental conditions and keep air inlets-

outlets free of dust. Please read 2.1. 

 

 

5.2 Fuses 

 

If the AC input fuse (1) is defective, be sure it is replaced by a compatible fuse from the same make and 

type. Fuse ratings: see chapter 7. 

 

 

5.3 Batteries 

 

5.3.1 General 

The service life of the battery is up to 6 years. 

As a healthy battery is critical to the UPS, keypad 'ON' allows a battery test (3.2.2). When the condition of 

the battery is critical, a 

'replace battery'

 alarm will be given (see 3.3). Charge the batteries for at least 10 

hours, switch the UPS off and back on, and perform a self test. If the alarm persists replace the batteries 

as soon as possible. 

 

5.3.2  Battery replacement  

  Warning: first read the safety rules in section 1.2. 

  When replacing the batteries, use the same number and voltage(V)/capacity(Ah). 

  Proper disposal or recycling of the batteries is required. Refer to your local codes for disposal 

requirements. 

  Never dispose of batteries in a fire: they may explode. 

  Do not open or mutilate batteries: their contents (electrolyte) may be extremely toxic. If exposed to 

electrolyte, wash immediately with plenty of water. 

  Avoid charging in a sealed container. 

  Never short circuit batteries. When working with batteries, remove watches, rings or other metal 

objects, and only use insulated tools. 

 

Battery replacement procedure (ML 350/500/700) 

 

NOTE:

 This procedure refers to the ML 350/500/700 models only. The batteries of the ML 1000 are not 

user replaceable, please contact your dealer. 

 

1  press keypad “OFF’ and remove the UPS input power cord from the AC mains supply 

2  remove UPS front panel (two screws on bottom side) 

3  pull out the battery and disconnect the battery wires 

4  connect the new battery (black -, red +); small sparks can occur, this is normal 

5  reinstall the new battery, do not pinch or clamp the wires 

6  reinstall UPS front panel. 

5  -  Maintenance

 

Summary of Contents for 1000 VA

Page 1: ...000 VA Manufactured by GE Digital Energy General Electric Company Telephone 41 0 91 850 51 51 CH 6595 Riazzino Locarno Fax 41 0 91 850 51 44 Switzerland Website www gedigitalenergy com Technology for...

Page 2: ...ATION 2 2 1 Installation Rules 2 2 Installation Procedure 3 OPERATION 4 3 1 Start up 3 1 1 Start up mains available 3 1 2 Start up mains not available battery start 3 2 Use Normal Operation 3 2 1 Norm...

Page 3: ...lly Connect the unit to a wall outlet for a period of approx 48 hours minimum every 3 months The shipping box contains a Digital Energy ML Series UPS a power cord a computer interface cable a CD ROM a...

Page 4: ...he output cord provided connect the computer to the appliance outlets 3 of the unit 4 Connect the mains cord of the UPS to a working grounded AC wall socket outlet The green LED LINE will blink now ma...

Page 5: ...g mains is poor the AVR boosts a low incoming voltage or reduces a high one The load receives a voltage within the normal range see chapter 7 3 2 2 Self test UPS operation and battery condition In cas...

Page 6: ...ible Replace battery 3 3 5 Mains on UPS output on UPS has failed to pass the previous self test Green on mains mode Green blinking 1x sec standby mode Red blinking 1x 30 sec Beeps 1x 30 sec Overload o...

Page 7: ...ted power during battery operation the UPS output will be switched off immediately during mains operation the UPS output will be switched off after 30 seconds 3 3 7 Self test The self test can be star...

Page 8: ...ng the batteries use the same number and voltage V capacity Ah Proper disposal or recycling of the batteries is required Refer to your local codes for disposal requirements Never dispose of batteries...

Page 9: ...e above No communication between computer and UPS Computer interface problem Check interface cable and attached computer Blown input fuse See above UPS operates on battery though mains is present Very...

Page 10: ...r factor 0 6 0 7 at 90 load Transfer time ms typically 4 max 10 Buck Boost voltage regulation if the input voltage is within the input voltage window the output voltage varies between 198 265Vac Batte...

Reviews: