PAGE 4: SETPOINT VALUES
RELAY CONFIGURATION
This page assigns trip and alarm functions to specific output relays (i.e. TRIP, ALARM, AUX. 1, AUX. 2
on the 169 Plus, or TRIP and ALARM on the model 169). Each trip/alarm function is assigned
separately to the appropriate relay or to "NO" relay. If an alarm feature is assigned to no relay, it can still
become active (i.e. cause the appropriate alarm message to be displayed if setpoints are exceeded) but
no output relay activation will occur. Possible assignments and factory values are shown below. Only
one TRIP may occur at any one time. TRIP functions must therefore be used to trip the motor.
Once one TRIP function is active, no other trip may occur.
4
Assign XXXXXXXXXXXXXXXX
to XXXXXXXXXXXX relay
For the model 169 Plus:
Feature Possible Assignments Factory Value
O/L TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
U/B TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
S/C TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
RAPID TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
STATOR RTD TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
RTD TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
G/F TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
ACCEL. TIME TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
PHASE REV. TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
STARTS/HOUR TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
SPEED SWITCH TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
DIFFERENTIAL TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
SINGLE PHASE TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
SPARE INPUT TRIP
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
START INHIBIT
TRIP or AUX. 1 or TRIP & AUX.1
TRIP RELAY
O/L WARNING
ALARM or AUX. 1 or AUX. 2 or NO
ALARM RELAY
G/F ALARM
ALARM or AUX. 1 or AUX. 2 or NO
ALARM RELAY
U/B ALARM
ALARM or AUX. 1 or AUX. 2 or NO
ALARM RELAY
U/C ALARM
ALARM or AUX. 1 or AUX. 2 or NO
ALARM RELAY
STATOR RTD ALARM
ALARM or AUX. 1 or AUX. 2 or NO
AUX. 1 RELAY
RTD ALARM
ALARM or AUX. 1 or AUX. 2 or NO
AUX. 1 RELAY
NO SENSOR ALARM
ALARM or AUX. 1 or AUX. 2 or NO
AUX. 1 RELAY
SELF-TEST FAIL
ALARM or AUX. 1 or AUX. 2 or NO
AUX. 2 RELAY
SPARE INPUT ALARM
ALARM or AUX. 1 or AUX. 2 or NO
NO RELAY
For the model 169:
Feature Possible Assignments Factory Value
O/L TRIP
(not shown)
TRIP RELAY
U/B TRIP
(not shown)
TRIP RELAY
S/C TRIP
(not shown)
TRIP RELAY
RAPID TRIP
(not shown)
TRIP RELAY
STATOR RTD TRIP
(not shown)
TRIP RELAY
RTD TRIP
(not shown)
TRIP RELAY
G/F TRIP
(not shown)
TRIP RELAY
ACCEL. TIME TRIP
(not shown)
TRIP RELAY
PHASE REV. TRIP
(not shown)
TRIP RELAY
STARTS/HOUR TRIP
(not shown)
TRIP RELAY
SINGLE PHASE TRIP
(not shown)
TRIP RELAY
O/L WARNING
ALARM or NO
ALARM RELAY
G/F ALARM
ALARM or NO
ALARM RELAY
U/B ALARM
ALARM or NO
ALARM RELAY
U/C ALARM
ALARM or NO
ALARM RELAY
STATOR RTD ALARM
ALARM or NO
ALARM RELAY
RTD ALARM
ALARM or NO
ALARM RELAY
NO SENSOR ALARM
ALARM or NO
ALARM RELAY
SELF-TEST FAIL
ALARM or NO
ALARM RELAY
Summary of Contents for 169
Page 12: ......
Page 14: ...2 INSTALLATION g GE Power Management 8 Figure 2 2 CT Dimensions ...
Page 17: ...2 INSTALLATION g GE Power Management 11 Figure 2 4 Relay Wiring Diagram AC control power ...
Page 19: ...2 INSTALLATION g GE Power Management 13 Figure 2 6 Relay Wiring Diagram Two Phase CTs ...
Page 20: ...2 INSTALLATION g GE Power Management 14 Figure 2 7 Relay Wiring Diagram DC Control Power ...
Page 28: ...2 INSTALLATION g GE Power Management 22 Figure 2 10 169 Drawout Relay Physical Dimensions ...
Page 29: ...2 INSTALLATION g GE Power Management 23 Figure 2 11 169 Drawout Relay Mounting ...
Page 31: ...3 SETUP AND USE g GE Power Management 25 Figure 3 1 Front Panel Controls and Indicators ...
Page 73: ...3 SETUP AND USE g GE Power Management 67 Figure 3 2 Standard Overload Curves ...
Page 74: ...3 SETUP AND USE g GE Power Management 68 A B Figure 3 3 Custom Curve Examples ...
Page 88: ...5 THEORY OF OPERATION g GE Power Management 82 Figure 5 1 Hardware Block Diagram ...
Page 90: ...5 THEORY OF OPERATION g GE Power Management 84 Figure 5 2 Firmware Block Diagram ...