GE Power Management
54
3$*(
'(6&5,37,21
5
RELAY ALARM
LATCHCODE = XX
This setpoint allows the choice of output relay latch attributes. A latched output relay must be manually
reset. An unlatched relay will be automatically reset when the condition that caused the relay activation
goes away.
Note: Trip functions must always be manually reset regardless of the Latchcode value chosen
here. This setpoint allows Alarm functions to be either manually or automatically resetable. The
Immediate O/L Alarm function will always be automatically reset regardless of the Latchcode.
latched = manual reset, unlatched = automatic reset
(see Table 3-6 for complete relay functions/configurations)
For the model 169 Plus:
Value Trip Alarm Aux. 1 Aux. 2
1
latched
unlatched
unlatched
latched
2 or 3
latched
latched
unlatched
latched
4 or 5
latched
unlatched
latched
latched
6 or 7
latched
latched
latched
latched
For the model 169:
Value Trip Alarm
1 or 4 or 5
latched
unlatched
2 or 3 or 6 or 7
latched
latched
Factory Value = 1
5
RELAY FAILSAFE
CODE = X
This code allows the choice of output relay fail-safe attributes. FS = fail-safe, NFS = non-fail-safe (see
Glossary). See Table 3-7 for complete relay functions/configurations.
For the model 169 Plus:
Value Trip Alarm Aux. 1 Aux. 2
1
FS
NFS
NFS
FS (see Figure 2-5)
2
NFS
FS
NFS
FS
3
FS
FS
NFS
FS
4
NFS
NFS
FS
FS
5
FS
NFS
FS
FS
6
NFS
FS
FS
FS
7
FS
FS
FS
FS
8
NFS
NFS
NFS
FS
For the model 169:
Value Trip Alarm
1 or 5
FS
NFS (see Figure 2-5)
2 or 6
NFS
FS
3 or 7
FS
FS
4 or 8
NFS
NFS
Factory Value = 1
Note: Due to the hardware configuration of the 169/169 Plus drawout relay this code cannot be
changed on any drawout models without corresponding hardware change.
Summary of Contents for 169
Page 12: ......
Page 14: ...2 INSTALLATION g GE Power Management 8 Figure 2 2 CT Dimensions ...
Page 17: ...2 INSTALLATION g GE Power Management 11 Figure 2 4 Relay Wiring Diagram AC control power ...
Page 19: ...2 INSTALLATION g GE Power Management 13 Figure 2 6 Relay Wiring Diagram Two Phase CTs ...
Page 20: ...2 INSTALLATION g GE Power Management 14 Figure 2 7 Relay Wiring Diagram DC Control Power ...
Page 28: ...2 INSTALLATION g GE Power Management 22 Figure 2 10 169 Drawout Relay Physical Dimensions ...
Page 29: ...2 INSTALLATION g GE Power Management 23 Figure 2 11 169 Drawout Relay Mounting ...
Page 31: ...3 SETUP AND USE g GE Power Management 25 Figure 3 1 Front Panel Controls and Indicators ...
Page 73: ...3 SETUP AND USE g GE Power Management 67 Figure 3 2 Standard Overload Curves ...
Page 74: ...3 SETUP AND USE g GE Power Management 68 A B Figure 3 3 Custom Curve Examples ...
Page 88: ...5 THEORY OF OPERATION g GE Power Management 82 Figure 5 1 Hardware Block Diagram ...
Page 90: ...5 THEORY OF OPERATION g GE Power Management 84 Figure 5 2 Firmware Block Diagram ...