Table 3-5 Standard Overload Curve Trip Times (in seconds)
MULTILIN STANDARD CURVE NUMBERS
Overload
Level
1
2
3
4
*
5
6
7
8
1.05
853
1707
2560
3414
5975
7682
10243
12804
1.10
416
833
1250
1666
2916
3750
5000
6250
1.20
198
397
596
795
1392
1789
2386
2982
1.30
126
253
380
507
887
1141
1521
1902
1.40
91
182
273
364
638
820
1093
1367
1.50
70
140
210
280
490
630
840
1050
1.75
42
84
127
169
297
381
509
636
2.00
29
58
87
116
204
262
350
437
2.25
21
43
64
86
150
193
258
323
2.50
16
33
50
66
116
150
200
250
2.75
13
26
39
53
93
119
159
199
3.00
10
21
32
43
76
98
131
164
3.50
7
15
23
31
54
69
93
116
4.00
5
11
17
23
40
52
69
87
4.50
4
9
13
18
31
40
54
68
5.00
3
7
10
14
25
32
43
54
5.50
2
5
8
11
20
26
35
44
6.00
2
5
7
10
17
22
30
37
6.50
2
4
6
8
14
19
25
31
7.00
1
3
5
7
12
16
21
27
7.50
1
3
4
6
11
14
19
23
8.00
1
2
4
5
9
12
16
20
*
Factory preset value
Summary of Contents for 169
Page 12: ......
Page 14: ...2 INSTALLATION g GE Power Management 8 Figure 2 2 CT Dimensions ...
Page 17: ...2 INSTALLATION g GE Power Management 11 Figure 2 4 Relay Wiring Diagram AC control power ...
Page 19: ...2 INSTALLATION g GE Power Management 13 Figure 2 6 Relay Wiring Diagram Two Phase CTs ...
Page 20: ...2 INSTALLATION g GE Power Management 14 Figure 2 7 Relay Wiring Diagram DC Control Power ...
Page 28: ...2 INSTALLATION g GE Power Management 22 Figure 2 10 169 Drawout Relay Physical Dimensions ...
Page 29: ...2 INSTALLATION g GE Power Management 23 Figure 2 11 169 Drawout Relay Mounting ...
Page 31: ...3 SETUP AND USE g GE Power Management 25 Figure 3 1 Front Panel Controls and Indicators ...
Page 73: ...3 SETUP AND USE g GE Power Management 67 Figure 3 2 Standard Overload Curves ...
Page 74: ...3 SETUP AND USE g GE Power Management 68 A B Figure 3 3 Custom Curve Examples ...
Page 88: ...5 THEORY OF OPERATION g GE Power Management 82 Figure 5 1 Hardware Block Diagram ...
Page 90: ...5 THEORY OF OPERATION g GE Power Management 84 Figure 5 2 Firmware Block Diagram ...