standard operation:
Wireless Monitor status LeD’s
• The wireless monitor receives data from the generator
every 10 minutes and displays the generator status
through 3 LED’s.
• Pressing the SYSTEM UPDATE button will provide
current generator status by flashing the status LED’s.
When pressed, all 3 LEDs will flash until the generator
status is received.
NOTICE
Generator control panel must be in AUTO mode or
no communication with monitor will occur.
• In order to conserve power and to extend battery life,
the LED’s are not lit continuously; instead they are
briefly flashed as indicated below.
NOTICE
During the weekly exercise cycle, the generator will
run for 20 minutes, but it will not supply power to the home.
During the exercise cycle, the monitor will continue blinking
the GENERATOR READY green LED.
• GENERATOR READY - When active, the green LED will
flash once every 7 seconds. The green LED indicates
that the generator is in AUTO mode and that it is
ready to run in the event of a loss of utility power.
• GENERATOR POWER - When active, the green LED will
flash every 7 seconds. The green LED indicates that
the generator is supplying power.
• SERVICE NEEDED - When active, the red LED will flash
in a sequence that corresponds to the service code.
For example, when Low Frequency scrolls across the
control board, the red LED will flash 5 times with a 3
second pause between series of blinks until it is reset
or the condition is corrected. When the red LED is lit,
contact your nearest authorized service dealer.
NOTICE
None of the conditions on the display unit can be
cleared at the wireless monitor. All alerts must be cleared at
the generator control panel.
NOTICE
Service conditions will only be displayed on the
basic monitor when the control board is placed in AUTO
mode.
other:
LeD Lighting codes
• Batteries Inserted - GENERATOR READY LED will light
for 5 seconds.
• Wireless Communication Lost - SERVICE NEEDED LED
will flash 20 fast pulses, then pause for 5 seconds,
and repeat the sequence until the communication
has been restored.
NOTICE
Communication lost issues can typically be resolved
by moving the wireless monitor closer, within the home, to
the standby generator.
• Linking Error or Not Linked - SERVICE NEEDED LED will
light for 4 seconds, pause for 4 seconds, and repeat
the sequence until a successful link is completed.
Before placing the generator system into service, inspect the
entire installation carefully, utilizing the Installation Checklist
on page 9.
This completes the installation and start-up instructions.
The operator’s manual provides full details on Operation,
Maintenance and Troubleshooting for this generator system.
installation inspection
NOT
for
REPRODUCTION
Summary of Contents for 20 kW Home
Page 10: ...10 Intentionally Left Blank N O T f o r R E P R O D U C T I O N ...
Page 41: ...41 NOTES N O T f o r R E P R O D U C T I O N ...
Page 42: ...42 NOTES N O T f o r R E P R O D U C T I O N ...
Page 43: ...43 Schematic Diagram Schematic Wiring Diagrams N O T f o r R E P R O D U C T I O N ...