g
GE
OPM_SGS_ISG_M22_M30_0US_V011.doc
14/38
Installation
Guide
SG Series
225 & 300 kVA
In case of parallel system, try to
place the UPS modules in
sequence of their numbers
(marked on the packing).
If the units are positioned “
side
by side
”, the side panels must be
mounted on all units.
UPS 1
UPS
3-4-5-6-7-8
UPS 2
S
G
S
_225-300_RP
A
d
is
p
os
ition_G
E
_01US
Fig. 3.4.1-5 RPA system disposition
3.4.2 Battery
location
Batteries require a well-ventilated room with controlled temperature to obtain reliable
operation.
The
Battery
can be install immediately adjacent to the UPS (left or right side) or remotely
from the UPS.
If the
Battery
is installed remotely from the UPS, a wall mounted DC disconnect device must
be installed within line-of-site to both the UPS and the
Battery
.
The optimal room temperature for the
Battery
is 68°F (20°C) to 77°F (25°C).
The life of valve-regulated batteries will be reduced by 50% for each additional
18°F
(10°C)
that the
Battery
ambient temperature is above
77°F
(25°C).
The
Battery System
associated with larger UPS is usually either rack mounted or installed in
multiple
Battery Cabinets
.
Installation and assembly must be made according to the local standards and
Battery
System
manufacturer‘s recommendations.
The
Battery Circuit Breaker
or
Battery Fuse Box
must be mounted as near as possible to the
Battery
.
Battery
installation and connection must be performed by qualified
personnel only.
Read all safety instructions before proceeding with the installation.