Not for
Reproduction
34
Initial Start-up (No Load)
The unit has been set-up for NG operation at the factory.
Fuel conversion, if needed, must be completed prior to
performing these steps. See
Fuel Conversion
.
Before operating the home generator or placing it into
service, inspect the entire installation carefully. Then begin
testing the system without any electrical loads connected,
as follows:
1. Remove two screws
A
that secure circuit breaker
cover to expose unit’s circuit breaker.
2. Connect an accurate frequency meter to line side of
generator’s main circuit breaker.
3. Set generator’s main circuit breaker to
ON
(closed) position.
4. Install 15 Amp fuse in control board.
5. Press and hold
MANUAL
button on control board for 3
seconds. Engine will start.
When the generator is started for the very first time, it will
require that air in the gaseous fuel lines be purged. This may
cause the engine to run roughly for a few minutes.
6. Listen for unusual noises, vibration or other
indications of abnormal operation. Check for oil leaks
while engine runs.
7. Let engine warm up for about 5 minutes to allow
internal temperatures to stabilize.
8. Check generator output at load side of circuit breaker.
Voltage should be 239 - 262 Volts, frequency should
be 62.0 - 62.5 Hz.
9. Check generator output between one generator
connection lug and neutral lug, then between
other generator connection lug and neutral lug.
In both cases, voltage reading should be between
112 and 125 Volts.
10. Push and hold
OFF
BUTTON
on control board until
engine stops.
11. Reinstall control box cover.
CAUTION
Installing the 15A fuse could cause the engine
to start at any time without warning resulting in minor or
moderate injury.
• Observe that the 15 Amp fuse has been removed from the control
panel for shipping.
• DO NOT install this fuse until all plumbing and wiring has been
completed and inspected.
MENU
ESC
AUTO
OFF
MANUAL
A
Summary of Contents for 40350
Page 10: ...N o t f o r R e p r o d u c t i o n 10 Intentionally Left Blank ...
Page 40: ...N o t f o r R e p r o d u c t i o n 40 NOTES ...
Page 41: ...N o t f o r R e p r o d u c t i o n 41 Schematic Diagram 10kW Schematic Wiring Diagrams ...
Page 42: ...N o t f o r R e p r o d u c t i o n 42 Wiring Diagram 10 kW J12 J19 ...
Page 43: ...N o t f o r R e p r o d u c t i o n 43 Schematic Diagram 8kW ...
Page 54: ...N o t f o r R e p r o d u c t i o n 10 Se dejó intencionalmente en blanco ...
Page 84: ...N o t f o r R e p r o d u c t i o n 40 Se dejó intencionalmente en blanco ...
Page 94: ...N o t f o r R e p r o d u c t i o n 10 Laissé en blanc intentionnellement ...
Page 124: ...N o t f o r R e p r o d u c t i o n 40 Laissé en blanc intentionnellement ...