Not for
Reproduction
25
Low Voltage connections to signal fault contacts, transfer switch communication and auxiliary 12VDC power are made via a
field connection terminal block in control board area. Compare this illustration with your generator to familiarize yourself with
the location of these connections.
System Connectors
A
- Two Pin Terminal Block
— Used to connect
utility 240 VAC from fuse block in ATS to the
control board. Connect only one wire per
terminal, Use #14 [2.5mm
2
] AWG minimum 300
volt wire.
B
- Fault Contacts
— Use 1 (N.O.), 2 (COM) and 3
(N.C.) to hook up a siren, light, etc. to alert you in
case of a fault. Contacts reverse state (1 [N.O.]
goes to 3 [N.C.] and vice versa) upon a fault
condition.
C
– Transfer Switch Communication (4 [TxRx] and
5 [TxRx GND])
—
Connect to transfer switch
control board for communication interface
using 18AWG [1mm
2
] twisted pair wire.
D
– 6 (+LED) and 7 (GND) Connection
—
Not
required for wireless monitor included with unit.
Available for optional hardwired remote system
status panel accessory, #6154.
E
- Eight Pin Terminal Block
— Used to connect
signal wires to the control board. Connect only
one wire per terminal.
F
- Power Connection (Line 1 and Line 2)
— Power
connection to transfer switch.
G
- Ground Connection
— Connect to transfer
switch ground wire.
H
- Neutral Connection
— Connect to transfer
switch neutral wire
• For power output connection (Line 1, Line 2, Neutral, and Ground), refer to the following table:
• For transfer switch communication use #18 AWG [1mm
2
] twisted pair conductors, no greater than 200 ft in length,
300 volt wire.
• When connecting to the terminal block, fasten only one wire to each connector screw.
• Torque terminal block screws to 4.4 in-lb [0.49 Newton meter].
• Torque circuit breaker connections to 45 in-lb [5 Newton meter].
* Metric system rounded for simplicity
1
2
3
4
5
6
7
8
25
26
L1
L2
N
auto
off
manual
ok
menu
esc
E
B
]
F
]
G
]
C
]
D
A
H
> 300V, 75° C
10 kW
8 kW
8 AWG [8 mm
2
] min. Cu
10 AWG [5 mm
2
] min. Cu
6 AWG [13 mm
2
] min. Al
8 AWG [8 mm
2
] min. Al
* Reference NEC 2014 table 310.15 • Use National Electric Code for correction factors and wire size calculations.
NOTICE
Neutral wire (H) must be connected to the
transfer switch Neutral wire.
DO NOT connect neutral and ground together
within the generator.
Summary of Contents for 40374
Page 10: ...N o t f o r R e p r o d u c t i o n 10 Intentionally Left Blank...
Page 40: ...N o t f o r R e p r o d u c t i o n 40 NOTES...
Page 41: ...N o t f o r R e p r o d u c t i o n 41 Schematic Diagram 10kW Schematic Wiring Diagrams...
Page 42: ...N o t f o r R e p r o d u c t i o n 42 Wiring Diagram 10 kW J12 J19...
Page 43: ...N o t f o r R e p r o d u c t i o n 43 Schematic Diagram 8kW...
Page 54: ...N o t f o r R e p r o d u c t i o n 10 Se dej intencionalmente en blanco...
Page 84: ...N o t f o r R e p r o d u c t i o n 40 Se dej intencionalmente en blanco...
Page 94: ...N o t f o r R e p r o d u c t i o n 10 Laiss en blanc intentionnellement...
Page 124: ...N o t f o r R e p r o d u c t i o n 40 Laiss en blanc intentionnellement...