ESL Wireless Smoke Detector

W i r e l e s s

ESL Commercial Wireless
Smoke Detector

60-992-900

Installation Instructions (PRELIMINARY)

Product Summary

The ESL Supervised Commercial Wireless Smoke Detector is UL Listed (UL 268) for use in commercial applications. The unit
combines a photoelectric smoke detector with an integrated fixed 135°F temperature and  rate-of-rise heat detector, and a
Learn Mode transmitter for use with compatible wireless control panels (see “Specifications” on back page).

Detector Operation

Under normal non-alarm conditions, the detector LED (light-emitting diode) flashes once every nine seconds while monitor-
ing the surrounding conditions. The detector transmits a supervisory signal every 64 minutes indicating its status, which the
panel receives and processes accordingly.

In an alarm condition due to smoke or heat, the LED changes from flashing to on and the built-in sounder emits a temporal 3
pattern (a repeated series of three beeps followed by a short pause). The detector also transmits an alarm signal, which the
panel receives and processes accordingly.

A built-in tamper switch activates whenever the detector is removed from its mounting base, causing the detector to transmit
a tamper signal which the panel receives and processes accordingly.

The detector is powered by two 3-volt lithium batteries (included). When the battery voltage gets low, the detector transmits
a low battery signal which the panel receives and processes accordingly. If the batteries are not replaced within seven days,
the detector’s built-in sounder emits a short beep or chirp every 45 seconds.

The detector also includes self-diagnostics, automatically adjusting its sensitivity accordingly to reduce the number of
detector cleanings. When cleaning becomes necessary, the detector has a field-replaceable optical chamber.

General Guidelines

Before mounting detectors, program (learn) them into panel memory and perform a sensor test from the detector’s
intended location, to ensure good RF communication to the panel.

Locate the detector in environmentally controlled areas where the temperature range is between 40° and 100°F (4.4° and
37.8°C) and the humidity is between 0 and 90% non-condensing.

Locate detectors away from ventilation sources that can prevent smoke from reaching the detector.

Locate ceiling mounted detectors in the center of the room or hallway, at least 4 inches (10cm) away from any walls or
partitions.

Locate wall mounted detectors so the top of the detector is 4 to 12 inches (10 to 31cm) below the ceiling.

In rooms with sloped, peaked, or gabled ceilings, locate detectors 3 feet (.9 meters) down or away from the highest point
of the ceiling.

When mounting to suspended ceiling tile, the tile must be secured with the appropriate fastener to prevent tile removal.

Note:

 Do not mount the detector to the metal runners of suspended ceiling grids. The metal runners can draw the magnet’s field away

from the detector’s reed switch, causing a false tamper alarm

 4300 Series

Wireless Smoke Detector

NX Series

Wireless Smoke Alarm/Detector

Figure 1. Detector Features

 LED

Test  button

Sounder 

vent

Temperature
sensor

Temperature
sensor

Summary of Contents for 60-992-900

Page 1: ...dingly If the batteries are not replaced within seven days the detector s built in sounder emits a short beep or chirp every 45 seconds The detector also includes self diagnostics automatically adjusting its sensitivity accordingly to reduce the number of detector cleanings When cleaning becomes necessary the detector has a field replaceable optical chamber General Guidelines Before mounting detec...

Page 2: ...talled as follows 1 In all sleeping rooms 2 Outside of each separate sleeping area in the immediate vicinity of the sleeping rooms 3 On each level of the dwelling unit including basement NFPA 72 11 5 4 1Existing Apartment Buildings Detection Where required by applicable laws codes or standards for the specified for specified occupancy approved single and multiple station smoke alarms shall be inst...

Page 3: ...er levels of the building Smoke detectors may not warn in time when fires are caused by smoking in bed explosions improper storage of flammables overloaded electrical circuits or other hazardous conditions Programming This section describes the basic steps for programming learning the detector into panel memory For complete programming instructions refer to the specific panel installation instruct...

Page 4: ...fic panel installation instructions 4 After testing all detectors exit from Sensor Test mode Smoke Test The smoke test verifies that the detector activates when detecting smoke that the transmitted signal is received by the receiver panel and that the panel reports the alarm to the central monitoring station The smoke test should be performed annually 1 Contact the central monitoring station to al...

Page 5: ...d dispose of them properly 4 Observing correct polarity insert two new 3V lithium batteries into the battery compartment and replace the cover 5 Reattach the detector to the mounting base 6 Test the system Sensitivity Test Use this test to check detector sensitivity 1 Press and hold the detector test button for two seconds then release it The detector transmits a test signal then performs a self t...

Page 6: ...and maintenance When installed and used properly it requires minimal maintenance The smoke detector should be tested weekly See Testing the Detector Sensitivity and Smoke Testing the Detector When a detector requires maintenance it extinguishes its LED and sends a signal to the control panel as described in the following table 7 Line the new field replaceable optical chamber up with the optical ba...

Page 7: ...sed in the proper packing of detectors returned under this warranty as GE Interlogix will not be responsible for warranty repairs to equipment damaged because of improper packing The above warranty is in lieu of all other express warranties and implied warranties of merchantability and fitness for a particular purpose are limited in duration for a period of THREE years from the date of manufacture...

Page 8: ...ignal output types smokealarm heatalarm tamper rate of rise alarm test low battery trouble supervisory Listing UL268 CSFM CE FCC For use with the following panels ITI Advent Commercial Fire 60 562 03 or 60 562 06 with software versions 1 62 and higher Product Ordering Patents 4 855 713 4 864 636 5 686 885 5 686 896 6 396 405 Model Description 60 992 900 ESL commercial wireless smoke detector two 3...

Reviews: