22
GE Zenith Controls
■
ZTG/ZTGD Operation and Maintenance Manual (70
R
-1000D)
Standard and Delay Transition
Each MX150 microprocessor based ATS controller
requires a Controls Power Supply (CPS) to apply line
voltage to the ATS operator via SCRs. Also required is
power for the MX150 printed circuit board and an
application of sensing voltage proportional to line voltage.
Controls Power Supply (CPS)
This is accomplished by the Controls Power Supply (CPS).
This method of switching operator voltage and applying
power and sensing voltage to the printed circuit board
isolates the MX150 from the line voltage, further protecting
the controller from harmful line transients.
Primary
CPS
CPS
Voltage
Assembly
Board
at 50/60 Hz
Part No.
No.
120V
50P-1224
50P-1200
208-220V
50P-1225
50P-1201
230-240V
50P-1226
50P-1202
277V
50P-1227
50P-1203
380-400V
50P-1228
50P-1204
416-440V
50P-1229
50P-1205
460-480V
50P-1230
50P-1206
575-600V
50P-1231
50P-1207