5.9 TIME OVERCURRENT CURVES
5 SETPOINTS
5
Table 5–15: IAC CURVE TRIP TIMES
MULTIPLIER
M
CURRENT
I
/
I
pkp
1.5
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
IAC EXTREMELY INVERSE
0.5
1.699
0.749
0.303
0.178
0.123
0.093
0.074
0.062
0.053
0.046
1.0
3.398
1.498
0.606
0.356
0.246
0.186
0.149
0.124
0.106
0.093
2.0
6.796
2.997
1.212
0.711
0.491
0.372
0.298
0.248
0.212
0.185
4.0
13.591
5.993
2.423
1.422
0.983
0.744
0.595
0.495
0.424
0.370
6.0
20.387
8.990
3.635
2.133
1.474
1.115
0.893
0.743
0.636
0.556
8.0
27.183
11.987
4.846
2.844
1.966
1.487
1.191
0.991
0.848
0.741
10.0
33.979
14.983
6.058
3.555
2.457
1.859
1.488
1.239
1.060
0.926
IAC VERY INVERSE
0.5
1.451
0.656
0.269
0.172
0.133
0.113
0.101
0.093
0.087
0.083
1.0
2.901
1.312
0.537
0.343
0.266
0.227
0.202
0.186
0.174
0.165
2.0
5.802
2.624
1.075
0.687
0.533
0.453
0.405
0.372
0.349
0.331
4.0
11.605
5.248
2.150
1.374
1.065
0.906
0.810
0.745
0.698
0.662
6.0
17.407
7.872
3.225
2.061
1.598
1.359
1.215
1.117
1.046
0.992
8.0
23.209
10.497
4.299
2.747
2.131
1.813
1.620
1.490
1.395
1.323
10.0
29.012
13.121
5.374
3.434
2.663
2.266
2.025
1.862
1.744
1.654
IAC NORMALLY INVERSE
0.5
0.578
0.375
0.266
0.221
0.196
0.180
0.168
0.160
0.154
0.148
1.0
1.155
0.749
0.532
0.443
0.392
0.360
0.337
0.320
0.307
0.297
2.0
2.310
1.499
1.064
0.885
0.784
0.719
0.674
0.640
0.614
0.594
4.0
4.621
2.997
2.128
1.770
1.569
1.439
1.348
1.280
1.229
1.188
6.0
6.931
4.496
3.192
2.656
2.353
2.158
2.022
1.921
1.843
1.781
8.0
9.242
5.995
4.256
3.541
3.138
2.878
2.695
2.561
2.457
2.375
10.0
11.552
7.494
5.320
4.426
3.922
3.597
3.369
3.201
3.072
2.969
IAC SHORT INVERSE
0.5
0.072
0.047
0.035
0.031
0.028
0.027
0.026
0.026
0.025
0.025
1.0
0.143
0.095
0.070
0.061
0.057
0.054
0.052
0.051
0.050
0.049
2.0
0.286
0.190
0.140
0.123
0.114
0.108
0.105
0.102
0.100
0.099
4.0
0.573
0.379
0.279
0.245
0.228
0.217
0.210
0.204
0.200
0.197
6.0
0.859
0.569
0.419
0.368
0.341
0.325
0.314
0.307
0.301
0.296
8.0
1.145
0.759
0.559
0.490
0.455
0.434
0.419
0.409
0.401
0.394
10.0
1.431
0.948
0.699
0.613
0.569
0.542
0.524
0.511
0.501
0.493
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...