GE Power Management
745 Transformer Management Relay
8-35
8 COMMUNICATIONS
8.3 MODBUS MEMORY MAP
8
745 SETUP
continued
1009
Slave Address
1 to 254
1
---
F1
254
100A
COM1 Baud Rate
---
---
---
F31
5 = 19200 Bd
100B
COM1 Parity
---
---
---
F73
0 = None
100C
COM1 Communication Hardware
---
---
---
F17
0 = RS485
100D
COM2 Baud Rate
---
---
---
F31
5 = 19200 Bd
100E
COM2 Parity
---
---
---
F73
0 = None
100F
Front Port Baud Rate
---
---
---
F31
5 = 19200 Bd
1010
Front Port Parity
---
---
---
F73
0 = None
1011
Local Reset Block
---
---
---
F87
0 = Disabled
1012
Remote Reset Signal
---
---
---
F88
0 = Disabled
1013
IRIG-B Signal Type
---
---
---
F84
0 = None
1014
Active Setpoint Group
---
---
---
F60
0 = Group 1
1015
Edit Setpoint Group
---
---
---
F74
4 = Active Grp
1016
Setpoint Group 2 Activate Signal
---
---
---
F88
0 = Disabled
1017
Setpoint Group 3 Activate Signal
---
---
---
F88
0 = Disabled
1018
Setpoint Group 4 Activate Signal
---
---
---
F88
0 = Disabled
1019
Clear Event Recorder Signal
---
---
---
F88
0 = Disabled
101A
DNP port
---
---
---
F99
0=None
101B
Reserved
101F
Reserved
DEFAULT
MESSAGES
1020
No. Of Default Messages Selected [read only]
0 to 30
1
---
F1
1
1021
Default Message #1 (2 registers)
---
---
---
F32
---
1023
Default Message #2 (2 registers)
---
---
---
F32
---
1025
Default Message #3 (2 registers)
---
---
---
F32
---
1027
Default Message #4 (2 registers)
---
---
---
F32
---
1029
Default Message #5 (2 registers)
---
---
---
F32
---
102B
Default Message #6 (2 registers)
---
---
---
F32
---
102D
Default Message #7 (2 registers)
---
---
---
F32
---
102F
Default Message #8 (2 registers)
---
---
---
F32
---
1031
Default Message #9 (2 registers)
---
---
---
F32
---
1033
Default Message #10 (2 registers)
---
---
---
F32
---
1035
Default Message #11 (2 registers)
---
---
---
F32
---
1037
Default Message #12 (2 registers)
---
---
---
F32
---
1039
Default Message #13 (2 registers)
---
---
---
F32
---
103B
Default Message #14 (2 registers)
---
---
---
F32
---
103D
Default Message #15 (2 registers)
---
---
---
F32
---
103F
Default Message #16 (2 registers)
---
---
---
F32
---
1041
Default Message #17 (2 registers)
---
---
---
F32
---
Table 8–6: 745 MEMORY MAP (Sheet 19 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...