8-38
745 Transformer Management Relay
GE Power Management
8.3 MODBUS MEMORY MAP
8 COMMUNICATIONS
8
115F
Reserved
ONLOAD TAP
CHANGER
1160
Winding With Tap Changer
---
---
---
F40
0 = None
1161
Number of Tap Positions
2 to 50
1
---
F1
33
1162
Minimum Tap Position Voltage
1 to 20000
---
kV
F90
610 = 61.0 kV
1163
Voltage Increment Per Tap
1 to 2000
---
kV
F91
50 = 0.50 kV
1164
Resistance Increment Per Tap
10 to 500
1
Ω
F1
33 = 33
Ω
1165
Reserved
↓
↓
↓
↓
↓
↓
↓
1167
Reserved
HARMONICS
1168
Harmonic Derating Estimation
---
---
---
F30
0 = Disabled
1169
THD Minimum Harmonic Number
---
---
---
F92
0 = 2nd
116A
THD Maximum Harmonic Number
---
---
---
F92
19 = 21st
116B
Reserved
↓
↓
↓
↓
↓
↓
↓
116F
Reserved
FLEXCURVES
1170
FlexCurve A Delay at 1.03
×
PKP
0 to 65000
1
ms
F1
0 ms
1171
FlexCurve A Delay at 1.05
×
PKP
0 to 65000
1
ms
F1
0 ms
1172
FlexCurve A Delay at 1.10
×
PKP
0 to 65000
1
ms
F1
0 ms
1173
FlexCurve A Delay at 1.20
×
PKP
0 to 65000
1
ms
F1
0 ms
1174
FlexCurve A Delay at 1.30
×
PKP
0 to 65000
1
ms
F1
0 ms
1175
FlexCurve A Delay at 1.40
×
PKP
0 to 65000
1
ms
F1
0 ms
1176
FlexCurve A Delay at 1.50
×
PKP
0 to 65000
1
ms
F1
0 ms
1177
FlexCurve A Delay at 1.60
×
PKP
0 to 65000
1
ms
F1
0 ms
1178
FlexCurve A Delay at 1.70
×
PKP
0 to 65000
1
ms
F1
0 ms
1179
FlexCurve A Delay at 1.80
×
PKP
0 to 65000
1
ms
F1
0 ms
117A
FlexCurve A Delay at 1.90
×
PKP
0 to 65000
1
ms
F1
0 ms
117B
FlexCurve A Delay at 2.00
×
PKP
0 to 65000
1
ms
F1
0 ms
117C
FlexCurve A Delay at 2.10
×
PKP
0 to 65000
1
ms
F1
0 ms
117D
FlexCurve A Delay at 2.20
×
PKP
0 to 65000
1
ms
F1
0 ms
117E
FlexCurve A Delay at 2.30
×
PKP
0 to 65000
1
ms
F1
0 ms
117F
FlexCurve A Delay at 2.40
×
PKP
0 to 65000
1
ms
F1
0 ms
1180
FlexCurve A Delay at 2.50
×
PKP
0 to 65000
1
ms
F1
0 ms
1181
FlexCurve A Delay at 2.60
×
PKP
0 to 65000
1
ms
F1
0 ms
1182
FlexCurve A Delay at 2.70
×
PKP
0 to 65000
1
ms
F1
0 ms
1183
FlexCurve A Delay at 2.80
×
PKP
0 to 65000
1
ms
F1
0 ms
1184
FlexCurve A Delay at 2.90
×
PKP
0 to 65000
1
ms
F1
0 ms
1185
FlexCurve A Delay at 3.00
×
PKP
0 to 65000
1
ms
F1
0 ms
1186
FlexCurve A Delay at 3.10
×
PKP
0 to 65000
1
ms
F1
0 ms
Table 8–6: 745 MEMORY MAP (Sheet 22 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...