WINDING 1
GROUND INST
OC 2
continued
21C4
Winding 1 Ground Inst O/C 2 Block
---
---
---
F87
0 = Disabled
21C5
Reserved
↓
↓
↓
↓
↓
↓
↓
21CF
Reserved
WINDING 2
GROUND INST
O/C 2
21D0
Winding 2 Ground Inst O/C 2 Function
---
---
---
F30
0 = Disabled
21D1
Winding 2 Ground Inst O/C 2 Target
---
---
---
F46
1 = Latched
21D2
Winding 2 Ground Inst O/C 2 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
21D3
Winding 2 Ground Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
21D4
Winding 2 Ground Inst O/C 2 Block
---
---
---
F87
0 = Disabled
21D5
Reserved
↓
↓
↓
↓
↓
↓
↓
21DF
Reserved
WINDING 3
GROUND INST
O/C 2
21E0
Winding 3 Ground Inst O/C 2 Function
---
---
---
F30
0 = Disabled
21E1
Winding 3 Ground Inst O/C 2 Target
---
---
---
F46
1 = Latched
21E2
Winding 3 Ground Inst O/C 2 Pickup
0.05 to 20.00
0.01
×
CT
F3
1000=10.00
×
CT
21E3
Winding 3 Ground Inst O/C 2 Delay
0 to 60000
1
ms
F1
0 ms
21E4
Winding 3 Ground Inst O/C 2 Block
---
---
---
F87
0 = Disabled
21E5
Reserved
↓
↓
↓
↓
↓
↓
↓
21EF
Reserved
WINDING 1
RESTD GND
FAULT
21F0
Winding 1 Restricted Ground Fault Function
---
---
---
F30
0 = Disabled
21F1
Winding 1 Restricted Ground Fault Target
---
---
---
F46
1 = Latched
21F2
Winding 1 Restricted Ground Fault Pickup
0.05 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
21F3
Winding 1 Restricted Ground Fault Slope
0 to 100
1
%
F1
10%
21F4
Winding 1 Restricted Ground Fault Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
21F5
Winding 1 Restricted Ground Fault Block
---
---
---
F87
0 = Disabled
21F6
Reserved
↓
↓
↓
↓
↓
↓
↓
21FF
Reserved
WINDING 2
RESTD GND
FAULT
2200
Winding 2 Restricted Ground Fault Function
---
---
---
F30
0 = Disabled
2201
Winding 2 Restricted Ground Fault Target
---
---
---
F46
1 = Latched
2202
Winding 2 Restricted Ground Fault Pickup
0.05 to 20.00
0.01
×
CT
F3
8 = 0.08
×
CT
2203
Winding 2 Restricted Ground Fault Slope
0 to 100
1
%
F1
10%
2204
Winding 2 Restricted Ground Fault Delay
0.00 to 600.00
0.01
s
F3
10 = 0.10 s
2205
Winding 2 Restricted Ground Fault Block
---
---
---
F87
0 = Disabled
2206
Reserved
↓
↓
↓
↓
↓
↓
↓
220F
Reserved
Table 8–6: 745 MEMORY MAP (Sheet 41 of 57)
GROUP
ADDR
(HEX)
DESCRIPTION
RANGE
STEP
VALUE
UNITS
FORMAT
CODE
FACTORY
DEFAULT
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...