GE Power Management
745 Transformer Management Relay
5-1
5 SETPOINTS
5.1 OVERVIEW
5
5 SETPOINTS 5.1 OVERVIEW
5.1.1 SETPOINT GROUPS
The 745 relay has a considerable number of programmable settings (setpoints) which makes it extremely flex-
ible. The setpoints have been grouped into a number of pages as shown below. If using the 745PC software
and not connected to a relay, you may have to select the File > Properties menu item and set the correct
options for your relay.
yy
SETPOINTS
yy
S1 745 SETUP
•
Passcode
•
Preferences (beeper, flash and default messages)
•
Communications (address, COM1 and COM2 parity / hardware type / baud rate)
•
Resetting
•
Clock
•
Default Messages
•
Scratch Pad
•
Installation
•
Upgrade options
yy
SETPOINTS
yy
S2 SYSTEM SETUP
•
Transformer
•
Windings 1, 2, and 3
•
Onload Tap Changer
•
Harmonics
•
FlexCurves
•
Voltage Input
•
Ambient Temperature
•
Analog Input
•
Demand Metering
•
Analog Outputs
yy
SETPOINTS
yy
S3 LOGIC INPUTS
•
Logic Inputs 1 to 16
•
Virtual Inputs 1 to 16
yy
SETPOINTS
yy
S4 ELEMENTS
•
Setpoint Group (active group and edit group)
•
Differential (percent differential; harmonic, energization, & 5
th
harmonic inhibits)
•
Instantaneous Differential
•
Phase Overcurrent (time and instantaneous for all windings)
•
Neutral Overcurrent (time and instantaneous for all windings)
•
Ground Overcurrent (time and instantaneous for all WYE windings)
•
Restricted Ground Fault (time and instantaneous for all windings)
•
Negative Sequence (time and instantaneous for all windings)
•
Frequency (underfrequency, frequency decay, and overfrequency)
•
Overexcitation (5
th
harmonic level and volts-per-hertz)
•
Harmonics (for all windings)
•
Insulation aging
•
Analog Input
•
Current Demand (for all windings)
•
Transformer Overload
•
Tap changer failure
yy
SETPOINTS
yy
S5 OUTPUTS
•
Output Relays
•
Trace Memory Triggering
•
Virtual Outputs
•
Timers
yy
SETPOINTS
yy
S6 TESTING
•
Output Relays (Forcing)
•
Analog Outputs (Forcing)
•
Simulation
•
Factory Service
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...