5.5 SETPOINTS S3 LOGIC INPUTS
5 SETPOINTS
5
5.5.3 VIRTUAL INPUTS
The Virtual Inputs setpoints are listed below:
y
VIRTUAL INPUTS
y
[ENTER] for more
This message indicates the start of the
VIRTUAL INPUTS
section. To continue
with these setpoints press
, or press
to go to the next
section.
y
VIRTUAL INPUT 1
y
[ENTER] for more
This message indicates the start of the virtual input 1 (2-16) setpoints. To
continue with these setpoints, press
key, or press
to go to
the next section.
INPUT 1 FUNCTION
Disabled
Range: Disabled / Enabled
Select
Enabled
if this logic input is to be used. Selecting
Disabled
will never
allow this logic input to achieve the ‘Asserted’ (or signaling) state.
INPUT 1 TARGET:
Self-Reset
Range: None / Latched / Self-Reset
Select
None
to inhibit the display of the target message when the input is
asserted. Thus an input whose “target type” is
None
will never disable the
LED self-test feature because can not generate a displayable target
message.
INPUT 1 NAME:
Virtual Input 1
Range: 18 alphanumeric characters
Press
to begin editing the name of the virtual input. The text may be
changed from
Virtual Input 1
one character at a time, using the
/
keys. Press
to store the edit and advance to the next
character position.
INPUT 1 PROGRAMMED
STATE: Not Asserted
Range: Not Asserted / Asserted
Select
Asserted
to place the virtual input in the signaling state. Select
Not
Asserted
to place the virtual input in the non-signaling state.
E N T E R
M E SSA G E
EN TE R
M E SSA G E
EN TE R
V A LU E
V AL U E
E N TE R
Summary of Contents for 745 TRANSFORMER MANAGEMENT RELAY
Page 30: ...2 8 745 Transformer Management Relay GE Power Management 2 3 SECURITY 2 GETTING STARTED 2 ...
Page 210: ...7 36 745 Transformer Management Relay GE Power Management 7 2 BLOCK DIAGRAMS 7 SCHEME LOGIC 7 ...
Page 322: ...9 12 745 Transformer Management Relay GE Power Management 9 3 USING 745PC 9 745 PC SOFTWARE 9 ...
Page 396: ...A 4 745 Transformer Management Relay GE Power Management A 1 FIGURES AND TABLES APPENDIXA A ...
Page 400: ...C 2 745 Transformer Management Relay GE Power Management C 1 WARRANTY INFORMATION APPENDIXC C ...
Page 406: ...vi 745 Transformer Management Relay GE Power Management ...
Page 407: ...GE Power Management 745 Transformer Management Relay NOTES ...