User Manual
SG Series 750 UL S2 & SG Series 750 T12 UL S2
`
Home\Setup\User
DISPLAY
UPS name
:
SG Series
Language :
ENGLISH
Contrast
V
LCD Display screen
UPS Name
The user can choose the name of the UPS
model shown on the main page (max. 9
characters).
Language
This parameter allows the choice of
language used to display the information.
Valid choices are:
English, German, Italian,
Spanish, French, Finnish, Polish, Portuguese,
Czech, Slovakian, Chinese, Swedish, Russian
and Dutch
.
Contrast
This parameter controls the contrast of the
LCD screen
in ten steps (0 – 9).
`
Home\Setup\User
eBoost
Enabled :
N
DAY OF WEEK
d1 d2
d3
d4
d5
d6
d7
HOURS / DAY
24 24 12 12 12 12 12
eBoost™ Operation Mode screen (option)
This screen is displayed only when
eBoost™ Operation
Mode
is available (option).
Enabled (Y / N / Wait)
Y/N
This parameter (values
Y
/
N
) enables or disables the
eBoost™ Operation Mode
.
If the value is
Y
and the current time is in the interval
for the current day, the
eBoost™ Operation Mode
is
active.
Wait
The
eBoost™ Operation Mode
configuration is being
updated.
In case of Parallel System
If
eBoost™ Operation Mode
is currently disabled
(N)
and
Q1
is closed, when programming it to enable
(Y)
the selected configuration will automatically be propagated to all units in the parallel system.
The activation / deactivation of
eBoost™ Operation Mode
is indicated each time in the event list.
In order to check the
inverter
function, at least
1 minute
of
VFI
Operation Mode
must be programmed during the
week (the
Y/N
parameter is automatically disabled if this condition is not satisfied).
In case this minimum time in
VFI Operation Mode
is not respected, the
eBoost™ Operation Mode
will be disabled.
If the value is
N
, the UPS is normally operating in
VFI / double conversion mode
at all times.
Status of the
Home Page
with UPS
functioning in
eBoost™ Operation Mode
.
DAY OF WEEK (d1 ÷ d7):
Enabling time in function of weekdays
Note:
the configuration of the activation schedule can only be
updated when
eBoost™ Operation Mode
is disabled
(Enabled: N)
.
For the weekdays from
d1
to
d7
(Saturday to Friday)
the edit mode (edit
day) allows to define time intervals when the UPS is operating in
eBoost™ Operation Mode
. The hour is given in 24-hour format.
These intervals are defined by:
eBoost START
:
The hour of the day after which the
eBoost™ Operation Mode
is enabled.
The
eBoost™ Operation Mode
is enabled until the following
eBoost STOP
time is reached (the
eBoost STOP
time of
the same day if this is later than the
eBoost START
time, the
eBoost STOP
time of the following day otherwise).
eBoost STOP
:
The hour of the day before which the
eBoost™ Operation Mode
is enabled.
The
eBoost™ Operation Mode
is enabled starting from the preceding
eBoost START
time (the
eBoost START
time of
the same day if this is earlier than the
eBoost STOP
time, the
eBoost START
time of the previous day otherwise).
Identical times for
eBoost START
and
eBoost STOP
maintain the existing mode only in case the previous command
was
eBoost START
and the following command will be
eBoost STOP
.
HOURS / DAY
:
The number of
eBoost™ Operation Mode
hours per weekday (from
d1
- Saturday
to
d7
- Friday
) is displayed in the
operation mode parameter window (ceiling value).