Modifications reserved
Page 52/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Operating Manual
SitePro 10-15-20-30-40 kVA / S8
7.3.3 Messages list
Code
Message
Meaning
4002
WATCHDOG RESET
The microprocessor has detected an incorrect operation:
transfers the load on mains and performs a program reset.
The inverter will restart automatically and will supply the
load.
4111
RECTIFIER MAINS OK
Rectifier input mains is again within the admitted tolerance
(voltage, frequency and phase).
4119
BATTERY TEST STARTED
Start of manual or automatic battery test.
Rectifier output voltage is decreased to the value defined
by parameters.
4120
BATTERY TEST STOPPED
End of manual or automatic battery test.
Rectifier output voltage is restored to floating voltage.
4161
RECTIFIER ON
Rectifier received the command to switch ON
4162
RECTIFIER OFF
Rectifier received the command to switch OFF for:
input mains out of tolerance / EPO / UDC max.
4163
GENERATOR ON
Customer interface (X1 - 11, 22) received a Gen-set ON
signal. Operating mode depend on setting of parameters.
4164
GENERATOR OFF
Customer interface (X1 - 11, 22) received a Gen-set OFF
signal. Function Bypass enabled depends on setting of
respective parameter.
4302
INVERTER CANNOT BE
TURNED ON
Inverter cannot be switched on because one of the
following conditions is still present:
-
Overtemperature.
-
Low battery voltage.
-
Inverter fuses.
-
Overload.
-
K7 opening failure.
-
High battery voltage.
-
DC low.
-
EPO.
4303
INVERTER CANNOT BE
TURNED OFF
Inverter cannot be switched OFF, because the load cannot
be switched to mains (voltage out of tolerance, not
synchrony, BP blocked).
4361
INVERTER ON
The command to start the inverter has been activated on
the control panel.
4362
INVERTER OFF
The command to switch OFF the inverter has been
activated by the control panel or automatically for alarm
presence.
4411
BYPASS MAINS OK
Bypass input mains is again within tolerance (voltage,
frequency and phase).
4500
COMMAND LOAD OFF
Disconnection of the load by opening K6 and K7 for:
EPO / Load Off / Overload / Stop operation
4521
NO BYPASS POWER
With the load supplied by electronic bypass, a mains failure
or K6 opening occurred.
4534
MULTIPLE LOAD TRANSFER
2 transfers inverter- mains has been detected in a short
time, defined by parameter (default 30 sec.).
4535
BYPASS LOCKED
Bypass to mains not enabled due to settings of parameters.
Contactor K6 is open.
4536
BYPASS FREE
Settings of parameters enable Bypass transfer on mains.
Contactor K6 can be closed.
4561
LOAD OFF
Key
“Load Off”
on the UPS Control Panel has been pressed,
with the output circuit breaker Q1 closed.