Modifications reserved
Page 60/99
OPM_SPE_XXX_10K_40K_8GB_V020.doc
Operating Manual
SitePro 10-15-20-30-40 kVA / S8
Example 5
:
An equivalent set of parameters for
Example 4
is.
Weekday
d1
- Saturday
d2
- Sunday
d3
- Monday
d4
- Tuesday
d5
- Wednesday
d6
- Thursday
d7
- Friday
SEM START
00:00 00:00 18:00 18:00 06:00 09:00 12:00
SEM STOP
23:59 20:00 18:00 06:00 06:00 09:00 13:00
SEM START
SEM STOP
The
SEM mode
is active from 18:00 of weekday
d3 - Monday
until 06:00 of weekday
d4 - Tuesday
(as
indicated by the
SEM STOP
time of weekday
d4 - Tuesday
).
The
SEM STOP
time of weekday
d3 - Monday
has no effect as it is followed by the
SEM STOP
time of
weekday
d4 - Tuesday
.
It can be, without change of meaning, any time between 18:00 and 23:59.
Similarly, the
SEM mode
is active from 18:00 of weekday
d4 - Tuesday
until 06:00 of weekday
d5 -
Wednesday
.
The
SEM START
time of weekday
d5 - Wednesday
has no effect as it is preceded by the
SEM START
time
of weekday
d4 - Tuesday
.
It can be, without change of meaning, any time between 00:00 and 06:00.
NOTE !
To avoid undesired
SEM mode
operation, verify:
•
Date and Time (first page of parameter).
•
SEM mode
screen how many hours of
SEM mode
operation have been selected
for each day of the week.
NOTE !
The
SEM mode
will become active only if the load is supplied from the inverter.