4–82
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SYSTEM
CHAPTER 4: SETPOINTS
Switching Device
The 869 supports two types of motor switching devices: breakers and contactors. A
breaker operation is controlled by two coils labeled “Trip” and “Close”. Each of them has to
be separately energized with a short pulse in order to change the state of the breaker. A
contactor operation is controlled by a single coil. When the coil is energized, the main
contacts are closed and when the coil is de-energized, the main contacts are open.
The user has to select either “Breaker” or “Contactor” and the selection has to match the
actual device type used. The selection is made in
Setpoints > System > Motor > Switching
Device Type.
Breakers
The breaker connection/disconnection to/from the power system (racked-out by the
breaker racking mechanism, or isolated by the associated disconnect switches on a fixed
circuit breaker) is provided by monitoring the contact input “BKR CONNECTED”. If the
contact input selected under the “BKR CONNECTED” setpoint is asserted, the breaker is
considered connected to the primary system. When the breaker is determined
disconnected, the breaker state is shown to be neither open, nor closed.
Path
:
Setpoints > System > Breakers > Breaker X
NAME
Range: Up to 13 alphanumeric characters
Default: BKR1
CONTACT INPUT 52a
Range: Off, Any FlexLogic operand
Default: Off
Selects the Contact Input connected to the breaker auxiliary contact 52a.
CONTACT INPUT 52b
Range: Off, Any FlexLogic operand
Default: Off
Selects the Contact Input connected to the breaker auxiliary contact 52b.
CONNECTED
Range: Off, Any FlexLogic operand
Default: Off
Select a contact input to show whether the breaker is connected (Racked-in, or
disconnect switches switched-on), or disconnected (racked-out, or disconnect switches
switched-off) from the system.
CLOSE RELAY SELECT
Range: Off, Relay 2
Default: Relay 2
Selection of "Relay 2" assigns the START command to Output Relay 2 (CLOSE/AUX). If "Off"
is selected, Auxiliary Relay 2 is available for selection in all elements with auxiliary relay
selection in the 869 and it is not activated by START command.
FASTPATH:
If “Relay 2” is selected, Auxiliary Relay 2 is not available for selection in any element.
Table 4-19: Breaker status depending on availability of contacts 52a and 52b
52a Contact Configured
52b Contact Configured
Breaker Status
Open
Closed
Yes
Yes
52a contact open
52b contact closed
52a contact closed
52b contact open
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...