4–172
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION
CHAPTER 4: SETPOINTS
ACCEL TIME FR. SPD 1-2
Range: 0.50 to 180.00 s in steps of 0.01
Default: 10.00 s
This setting is provided to select maximum accelerating time from speed 1 to speed 2
when motor is switched from low-to-high speed.
BLOCK
Range: FlexLogic Operand
Default: Off