CHAPTER 4: SETPOINTS
PROTECTION
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–241
TRIP MODE
Range: Blinder Exit, MHO Exit
Default: MHO Exit
Selecting "Blinder Exit" results in an instantaneous trip after the last step in the out-of-
step tripping sequence is completed (the impedance locus leaves the opposite blinder).
The Blinder Exit trip mode stresses the circuit breakers as the currents at that moment
are high (the electromotive forces of the two equivalent systems are close to 180° apart).
Selecting "MHO Exit" results in a trip at the moment when the impedance locus leaves
the mho characteristic. The MHO Exit trip mode relaxes the operating conditions for the
breakers as the currents at that moment are low, preventing the breakers from a
maximum recovery voltage during interruption. The selection should be made
considering the capability of the breakers in the system.
POS SEQ CURR SUPERVISION
Range: 0.05 to 10.00 x CT in steps of 0.01 x CT
Default: 1.00 x CT
A common overcurrent pickup level supervises the left and right blinder characteristics.
The supervision responds to the positive sequence current.
SEAL-IN DELAY
Range: 0.000 to 1.000 s in steps of 0.001 s
Default: 0.100 s
The out-of-step trip FlexLogic operand (OOS OP) is sealed-in for the specified period of
time. The sealing-in is crucial to the MHO EXIT trip mode, as the original trip signal is a
very short pulse occurring when the impedance locus leaves the mho characteristic
after the out-of-step sequence is completed.
BLOCK
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
OUTPUT RELAY X
For details see
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Latched, Disabled
Default: Latched
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...