4–278
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING
CHAPTER 4: SETPOINTS
current signal is multiplied by the corresponding phase or line voltage signal V
a
*I
a
. This
approach allows to increase the contrast between fault signature by shifting fault
characteristic frequency closer to the DC in the whole spectrum.
The FFT of the resultant multiplied signal is shown in the following figure. Comparison of
the two figures shows a clear contrast between fault signature and fundamental
frequency in coherent demodulated signal compared to only current FFT method signal.
Path
:
Setpoints > Monitoring > Broken Rotor Bar
FUNCTION
Range: Disabled, Alarm, Latched Alarm, Configurable
Default: Disabled
The selection of
Alarm, Latched Alarm
or
Configurable
setting enables the Broken
Rotor Bar function. When the
Alarm
function is selected and the Broken Rotor Bar
operates, the LED “ALARM” flashes, and self-resets, when the operating conditions are
cleared.When the
Latched Alarm
function is selected, and the Broken Rotor Bar
operates, the LED “ALARM” flashes during the Broken Rotor Bar operating condition, and
is steady lit after the conditions are cleared. The LED “ALARM” is cleared by issuing the
reset command.When the
Configurable
function is selected, the ALARM LED does not
turn on automatically. They need to be configured using their own menus and flexlogic
operands.
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...