4–326
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING
CHAPTER 4: SETPOINTS
Path:
Setpoints > RTD Temperature > RTD 1[X]
TRIP FUNCTION
Range: Disabled, Trip, Configurable
Default: Disabled
For Transformer applications, if a trip is not required from the RTD, the user can select
“Configurable”. The “Configurable” setting enable the RTD without producing trip.
NAME
Range: Up to 13 alphanumeric characters
Default: RTD 1
TYPE
Range: 100
Ω
Platinum, 100
Ω
Nickel, 120
Ω
Nickel, 10
Ω
Copper
Default: 100
Ω
Platinum
Selects the type of the RTD used.
APPLICATION
Range: None, Stator, Bearing, Ambient, Other
Default: None
The setting allows each individual RTD to be assigned to a group application. This is
useful for some applications, which require group measurement. The setting “None”
means that the RTD operates individually and is not part of any RTD group. Common
groups are provided for needs at rotating machines applications such as “Ambient” of
“Bearing”.
VOTING
Range: Off, RTD 1, RTD 2….RTD 12
Default: Off
This setting selects the RTD that must also exceed this RTD’s Trip Temperature for a trip
to occur. Selecting the same RTD to which the element is related to, has the same effect
as selecting “Off”.
TRIP TEMPERATURE
Range: 1°C to 250°C in steps of 1°C (33°F to 482°F in steps of 2°F)
Default: 155°C (311°F)
TRIP PICKUP DELAY
Range: 0 s to 600 s in steps of 1 s
Default: 2 s
TRIP DROPOUT DELAY
Range: 0 s to 600 s in steps of 1s
Default: 0 s
TRIP OUTPUT RELAY X
For details see
ALARM FUNCTION
Range: Disabled, Alarm, Latched Alarm
Default: Disabled
ALARM TEMPERATURE
Range: 1°C to 250°C in steps of 1°C (33°F to 482°F in steps of 2°F)
Default: 130°C (266°F)
ALARM PICKUP DELAY
Range: 0 s to 600 s in steps of 1 s
Default: 2 s
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...