CHAPTER 4: SETPOINTS
CONTROL
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–341
Figure 4-145: Time Between Starts logic diagram
Restart Delay
The Restart Delay feature is used to ensure that a certain amount of time passes between
the time a motor is stopped and the restarting of that motor. This timer feature can be very
useful for some process applications or motor considerations. If a motor is on a down-hole
pump, after the motor stops, the liquid can fall back down the pipe and spin the rotor
backwards. It is very undesirable to start the motor at this time.
The Restart Delay inhibit lockout will remain active (it may be used as a backspin timer)
when the Emergency Restart input is asserted.
The status of the Restart Delay element (including the time) is stored into a non-volatile
memory and remains in the memory after the power is removed from the 869. When the
power is restored, the Restart Delay element continues working normally using the
information collected before the power loss if the real time clock worked properly during
the power loss.
Path:
Setpoints > Control > Motor Starting > Start Supervision > Restart Delay
FUNCTION
Default: Disabled
Range: Disabled, Enabled
MINIMUM TIME
Range: 0 to 65000 s in steps of 1s
Default: 0 s
Sets the amount of time following stop before a start control is permitted.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched
894086A2.cdr
FLEXLOGIC OPERANDS
Time Btwn Star PKP
Function
SETPOINT
Enabled = 1
SETPOINT
Motor Starting
FLEXLOGIC OPERANDS
Minimum Time
Time Btwn Start OP
ACTUAL VALUES
Time Btwn Starts LO Time
Emergency Restart
FLEXLOGIC OPERAND
STATUS
Ti
m
e
r
Re
se
t
FLEXLOGIC OPERANDS
AN
D
Tmin
0
AN
D
LED : Start
Inhibit
Motor Stopped
Motor Tripped
OR
FLEXLOGIC OPERANDS
Start Inhibit
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...