CHAPTER 4: SETPOINTS
CONTROL
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
4–357
BYPASS REM BLK OPEN
Range: Off, Any FlexLogic operand
Default: Off
This setting specifies selection of an input which when asserted bypasses the asserted
remote block open signal. Open command is permitted for the breaker.
BYPASS REM BLK CLOSE
Range: Off, Any FlexLogic operand
Default: Off
This setting specifies selection of an input which when asserted bypasses the asserted
remote block close signal. Close command is permitted for the breaker.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset