6–18
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
POWER FACTOR
CHAPTER 6: METERING
Power Factor
The power factor value input to the power factor element(s) is displayed here. Note that
the value may not be equal to the power factor value displayed under Metering > Power 1
since the supervision conditions are applied in the element.
Path
:
Metering > Power Factor 1(X)
POWER FACTOR 1(X)
Range: -0.99 to 1.00 in steps of 0.01
Default: 0.00
Current Demand 1
NOTE
NOTE:
The number of Current Demand supported is Order Code dependent.
The relay measures Current Demand on each phase, and three phase Demand for real,
reactive, and apparent power. These parameters can be monitored to reduce supplier
Demand penalties or for statistical metering purposes. Demand calculations are based on
the measurement type selected under MONITORING/FUNCTIONS/DEMAND. For each
quantity, the relay displays the Demand over the most recent Demand time interval, the
maximum Demand since the last maximum Demand reset, and the time and date stamp
of this maximum Demand value. Maximum Demand quantities can be reset to zero with
the RECORDS/CLEAR RECORDS/MAX CURRENT DEMAND.
Path
:
Metering > Current Demand 1
Reset (J1 Reset Demand Date/Time) MM/DD/YY 00:00:00
Phase A Demand (J1 Ph A Demand)
Range: 0.000 to 12000.000 A
Phase B Demand (J1 Ph B Demand)
Range: 0.000 to 12000.000 A
Phase C Demand (J1 Ph C Demand)
Range: 0.000 to 12000.000 A
Maximum Phase A Demand (J1 Max Ph A Demand)
Range: 0.000 to 12000.000 A
Maximum Phase B Demand (J1 Max Ph B Demand)
Range: 0.000 to 12000.000 A
Maximum Phase C Demand (J1 Max Ph C Demand)
Range: 0.000 to 12000.000 A
Date/Time Phase A Demand (J1 Date/Time Ph A Demand) MM/DD/YY HH:MM:SS
Date/Time Phase B Demand (J1 Date/Time Ph B Demand) MM/DD/YY HH:MM:SS
Date/Time Phase C Demand (J1 Date/Time Ph C Demand) MM/DD/YY HH:MM:SS
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...