CHAPTER 6: METERING
POWER DEMAND
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
6–19
Power Demand
This menu shows the real, reactive, and apparent power demands along with their
maximums. The maximums can be cleared by resetting them from Records \Clear Records
\Max Real /Reactive /Apparent Demand.
Path
:
Metering > Power Demand 1(X)
Reset (Reset Dmd Date/Time) MM/DD/YY 00:00:00
Real Demand (Real Dmd)
Range: 0.0 kW to 214748364.7 kW
Maximum Real Demand (Max Real Dmd)
Range: 0.0 kW to 214748364.7 kW
Date/Time Real Demand (Date/Time Real Dmd) MM/DD/YY 00:00:00
Reactive Demand (Reactive Dmd)
Range: 0.0 kvar to 214748364.7 kvar
Maximum Reactive Demand (Max Reactive Dmd)
Range: 0.0 kvar to 214748364.7 kvar
Date/Time Reactive Demand (Date/Time Reactive Dmd) MM/DD/YY 00:00:00
Apparent Demand (Apparent Dmd)
Range: 0.0 kVA to 214748364.7 kVA
Maximum Apparent Demand (Max Apparent Dmd)
Range: 0.0 kVA to 214748364.7 kVA
Date/Time Apparent Demand (Date/Time Apparent Dmd) MM/DD/YY 00:00:00
Directional Power
Path
:
Metering > Directional Power
The effective operating quantities of the sensitive directional power elements are
displayed here. The display may be useful to calibrate the feature by compensating the
angular errors of the CTs and VTs with the use of the RCA and CALIBRATION settings.
Directional Power 1 (Directional Power 1)
Range: -214748364.8 kW to 214748364.7 kW
Default: 0.0 kW
Directional Power 2 (Directional Power 2)
Range: -214748364.8 kW to 214748364.7 kW
Default: 0.0 kW
Directional Power X (Directional Power X)
Range: -214748364.8 kW to 214748364.7 kW
Default: 0.0 kW
Summary of Contents for 869
Page 10: ...VIII 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ...
Page 127: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 49 ...
Page 129: ...CHAPTER 3 INTERFACES SOFTWARE INTERFACE 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL 3 51 ...
Page 538: ...4 406 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 4 SETPOINTS ...
Page 578: ...6 22 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXELEMENTS CHAPTER 6 METERING ...
Page 592: ...7 14 869 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CLEAR RECORDS CHAPTER 7 RECORDS ...