DEH40157 

DEH40157   Rev.No.01 

1

    

A-Series 

®

 II Panelboards

 

AD/AE/AQ Type P & N Power Panel 
TEY Three-Phase Circuit Breaker Kits 
 

Introduction 

 

These instructions describe the installation of TEY three-phase circuit breaker kit into an 
A-Series

®

 II panelboard. These kits are for use in panelboards ordered with Un-Specified 

Space.  
The catalog number for 6pole TEY breaker kit is ASPP6EY6D  

Parts List ASPP6EY6D 

Table 1. 

ITEM # 

DESCRIPTION 

PART # 

QTY

A & C PHASE 200A STRAP 

315A7049P10 

STRAP, CENTER  

315A7048P20 

3 3X 

BRANCH 

BASE 

911E347P3 

THREAD ROLLING SCREW & WASHER      315A7034P6 

FILLER PLATE, TEY 

139C5503P129

 

SCREWS , #10-32 X 3/8 

N722P16006B6 

 

Installation 
 
WARNING

Before attempting to install one of these kits, remove all power from the 

panelboard.

 

 
Use the following procedure to install a TEY circuit breaker kit. Call-out numbers in the 
illustrations and numbers in brackets in the text refer to the Item Numbers in Table 1. 
Installation of a three-pole kit is illustrated in Figure 1. 
 

1.  Remove the interior assembly from its packaging and verify that all parts are 

present, as given in the parts list. 

2.  Remove the 8 screws (600A and 800A panels) securing the dead front to 

panelboard interior. Lift off the dead front and place it and the screws aside. 

3.  Remove the circuit breaker kit from its packaging and verify that all parts are 

present, as given in the packing list. 

4.  Refer fig no.1 to mount the breaker on interior. Place 3X base [3] adjacent to the  

crossbar[7] to locate the mounting hole for the B phase strap [2]. Remove 3X base 
[3] and screw the B phase Strap [2] into place using screw [4]. Then mount the 
straps for A and C phase [1] into place using screws [4]. All phase straps should 
be clamped with main bus using screws [4] with a maximum of 60 in-lb torque. 

Summary of Contents for A II Series

Page 1: ...e to install a TEY circuit breaker kit Call out numbers in the illustrations and numbers in brackets in the text refer to the Item Numbers in Table 1 Installation of a three pole kit is illustrated in Figure 1 1 Remove the interior assembly from its packaging and verify that all parts are present as given in the parts list 2 Remove the 8 screws 600A and 800A panels securing the dead front to panel...

Page 2: ...e breaker as shown in fig 1 such that breaker strap hole aligns with breaker mounting strap tapped hole and other end of breaker snaps with 3X base lancing slot provided and then tighten terminal screws completely with 27 36 in lb 6 Remove the eight screws 6 of existing one filler plates from dead front where the TEY breaker needs to be installed as illustrated in Figure 2 ...

Page 3: ... filler plate 5 over the dead front so that the four same size holes line up with the threaded holes of the dead front as illustrated in Figure 3 Fasten filler plate to the dead front with four 10 32 x 3 8 screws 6 tightened to 27 36 in lb 8 Reattach the dead front to the interior with the 8 screws removed in step 2 Tighten the screws to 27 36 in lb ...

Page 4: ...SG or SF TFJ or SE TED TQD as shown in Figure 4 then gap between the breakers dim A has to be followed as mentioned in Table 2 Replace the subsequent blank filler of dead front with TEY filler plate given in kit ASPP6EY6D using steps 9 to 11 13 If TEY breaker has to installed immediate after crossbar as shown in Figure 5 then gap between the breaker and crossbar has to be 0 06inch ...

Page 5: ...DEH40157 DEH40157 Rev No 01 5 Figure 4 Distance between breakers Table 2 Distance between breakers Breaker A in SG 0 582 SF TFJ 1 875 SE TED 6P 1 875 FB TQD 6P 1 875 ...

Page 6: ...ariations in equipment nor do they provide for every possible contingency that may be met in connection with installation operation or maintenance Should further information be desired or should particular problems arise that are not covered sufficiently for the purchaser s purposes the matter should be referred to the GE Company ...

Reviews: