OUTDOOR TECHNICAL OVERVIEW
ENGLISH
Topic Title
B-23
DIP Switch Settings
WJ26X25054 - Service Monitor Board DIP Switch Settings
Outdoor Central
Control Address
SW6-1
SW6-2
SW6-3
SW6-4
0
OFF
OFF
OFF
OFF
1
OFF
OFF
OFF
ON
2
OFF
OFF
ON
OFF
3
OFF
OFF
ON
ON
4
OFF
ON
OFF
OFF
5
OFF
ON
OFF
ON
6
OFF
ON
ON
OFF
7
OFF
ON
ON
ON
8
ON
OFF
OFF
OFF
9
ON
OFF
OFF
ON
10
ON
OFF
ON
OFF
11
ON
OFF
ON
ON
12
ON
ON
OFF
OFF
13
ON
ON
OFF
ON
14
ON
ON
ON
OFF
15
ON
ON
ON
ON
Outdoor central control address settings
Definition
SW1-1
SW1-2
SW1-3
SW1-4
Factory default
OFF
OFF
OFF
OFF
Forced heating
ON
OFF
OFF
OFF
Forced cooling
OFF
ON
OFF
OFF
Rated operation
OFF
OFF
ON
OFF
Time defrost valid: Defrost initiates if
needed when the compressor has been on
for 10 minutes continuously and 50 minutes
cumulative. Termination conditions are the
same as demand defrost.
OFF
OFF
OFF
ON
Wiring check active*
ON
ON
ON
ON
Description
SW7-1 SW7-2 SW7-3 SW7-4 SW7-5 SW7-6 SW7-7 SW7-8
USA energy efficiency test mode for High Wall unit OFF*
OFF*
----
----
----
----
----
----
USA energy efficiency test mode for Duct unit
ON
OFF
----
----
----
----
----
----
Reserved
----
OFF*
----
----
----
----
----
Reserved
----
----
----
OFF*
----
----
----
----
Reserved
----
----
----
----
OFF*
----
----
----
Reserved
----
----
----
----
----
OFF*
----
----
North American region
----
----
----
----
----
----
ON*
----
Non-North American region
----
----
----
----
----
----
OFF
----
Quiet operation valid
----
----
----
----
----
----
----
OFF*
SW6 DIP Switch Settings
SW1 DIP Switch Settings
SW7 DIP Switch Settings
*Factory Default Setting
*See page B-18 for Wiring Error Check.