57
16. Inhibit/uninhibit RAS/DGP
Use this function to inhibit remote arming stations (RASs) and data gathering panels (DGPs), i.e. exclude fault
and tamper messages (system alarms) from a RAS or DGP to the security system.
This function is used if a RAS or DGP has generated a system alarm, or is out of service, and needs to be
inhibited while awaiting service.
To inhibit/uninhibit RASs/DGPs
1. Access menu option 16.
The display shows:
1-RAS, 2-DGP Inhibit / Uninhibit
0-Exit, Menu:
2. Enter
1
for RAS or
2
for DGP, and press
[ENTER]
.
•
If RAS is selected, the display shows any RASs that are inhibited:
No RAS's Are Inhibited
Inhibit RAS:
•
If DGP is selected, the display shows any DGPs that are inhibited:
No DGP's Are Inhibited
Inhibit DGP:
3. Enter the RAS/DGP number to be inhibited.
•
If the number entered is not recorded, it is added and displayed.
•
If the number entered is already recorded, it is deleted and removed from the display.
or press
[ENTER]
to return to the menu.
Inhibiting a DGP does NOT inhibit the alarm zones on that DGP, but does disable DGP offline/online reporting (TAMPER
switch).
Inhibiting a RAS or DGP also resets any system alarm generated by the RAS or DGP.
See also:
Types of Alarms - System Alarms, page