6 Parameters
6.1 Parameter Overview
6.1.1 Parameter List
Nr.
Title
Default value
Range
Conversion in-
dex
Data
type
O-01
Control Site
Dig. and ctrl. word [0]
[0 - 2]
-
5
O-02
Control Source
Drive RS485 [0]
[0 - 4]
-
5
O-03
Control Timeout Time
1 s
0.1 - 18000
- 1
7
O-04
Control Timeout Function
Off [0]
[0 - 10]
-
5
O-05
End-of-timeout Function
Hold set-up [0]
[0 - 1]
-
5
O-06
Reset Control Timeout
Do not reset [0]
[0 - 1]
-
5
O-07
Diagnosis Trigger
Disable [0]
[0 - 3]
-
5
O-10
Control Profile
Drive profile protocol [0]
[0 - x]
-
5
O-30
Protocol
Drive
O-31
Address
1
[0 – 255]
O-32
Baudrate
9600
[0 – 7]
O-33
Parity/Stop Bits
No Parity, 1 Stop Bit
O-35
Minimum Response Delay
10mS
O-36
Max Response Delay
5000mS
O-37
Max Inter-Char Delay
25.00mS
O-50
Coasting Select
Logic OR [3]
[0 - 3]
-
5
O-52
DC Brake Select
Logic OR [3]
[0 - 3]
-
5
O-53
Start Select
Logic OR [3]
[0 - 3]
-
5
O-54
Reversing Select
Logic OR [3]
[0 - 3]
-
5
O-55
Setup Select
Logic OR [3]
[0 - 3]
-
5
O-56
Preset Reference Select
Logic OR [3]
[0 - 3]
-
5
BN-70
BACnet Device Instance
1
[1-4194304]
-
BN-72
MS/TP Max Masters
127
[1-127]
-
BN-73
MS/TP Max Info Frames
BN-74
“I am” Service
Once at powerup [0]
[0-1]
-
BN-75
Initialisation Password
“admin”
String[19]
Table 6.1: BACnet specific parameter list
Please refer to the
AF-600 FP Drive Operating Instructions
for a comprehensive parameter list or to the
AF-600 FP Drive Programming Guide
for detailed descriptions
of parameters.