5.1.4 Navigation Keys
Navigation keys are used for programming functions and
moving the display cursor. The navigation keys also
provide speed control in local (hand) operation. Three
drive status indicator lights are also located in this area.
Key
Function
Back
Reverts to the previous step or list in the menu
structure.
Cancel
Cancels the last change or command as long as
the display mode has not changed.
Info
Press for a definition of the function being
displayed.
Navigation
Keys
Use the four navigation arrows to move between
items in the menu.
OK
Use to access parameter groups or to enable a
choice.
Light
Indicator
Function
Green
ON
The ON light activates when the
drive receives power from AC line
voltage, a DC bus terminal, or an
external 24V supply.
Yellow
WARN
When warning conditions are met,
the yellow WARN light comes on
and text appears in the display
area identifying the problem.
Red
ALARM
A fault condition causes the red
alarm light to flash and an alarm
text is displayed.
5.1.5 Operation Keys
Operation keys are found at the bottom of the keypad.
Key
Function
Hand
Press to start the drive in local control.
•
Use the navigation keys to control drive
speed
•
An external stop signal by control input or
serial communication overrides the local hand
Off
Stops the motor but does not remove power to
the drive.
Auto
Puts the system in remote operational mode.
•
Responds to an external start command by
control terminals or serial communication
•
Speed reference is from an external source
Reset
Resets the drive manually after a fault has been
cleared.
5.2 Backup and Copying Parameter Settings
Programming data is stored internally in the drive.
•
The data can be uploaded into the keypad
memory as a storage backup
•
Once stored in the keypad, the data can be
downloaded back into the drive
•
Data can also be downloaded into other
adjustable frequency drives by connecting the
keypad into those units and downloading the
stored settings. (This is a quick way to program
multiple units with the same settings.)
•
Initialization of the drive to restore factory default
settings does not change data stored in the
keypad memory
WARNING
UNINTENDED START!
When the drive is connected to AC line power, the motor
may start at any time. The drive, motor, and any driven
equipment must be in operational readiness. Failure to
comply could result in death, serious injury, equipment or
property damage.
User Interface
AF-600 FP Quick Guide
20
DET-759A
5
5