Protection and Features:
•
Electronic thermal overload motor protection against overload.
•
Temperature monitoring of the heatsink ensures that the drive trips if the temperature reaches 203° F ± 9° F [95
°
C ± 5
°
C]. An overload temperature cannot be reset until the temperature of the heatsink is below 158° F ± 9° F
[70
°
C ± 5
°
C] (Guideline - these temperatures may vary for different power sizes, enclosures, etc.). The drive has
an auto derating function to avoid it's heatsink reaching 203° F [95
°
C].
•
The drive is protected against short-circuits on motor terminals U, V, W.
•
If a line phase is missing, the drive trips or issues a warning (depending on the load).
•
Monitoring of the intermediate circuit voltage ensures that the drive trips if the intermediate circuit voltage is too
low or too high.
•
The drive is protected against ground faults on motor terminals U, V, W.
Specifications
AF-600 FP Quick Guide
36
DET-759A
8
8