Voltage
Power Size
Clearance a/b
200-240 V
0.25-3.7 kW 1/3-5 HP
100 mm/4 in
5.5-30 kW 7.5-40 HP
200 mm/8 in
>30 kW/40 HP
225 mm/10 in
380-480 V
0.37-7.5 kW 1/2-10 HP
100 mm/4 in
11-55 kW 15-75 HP
200 mm/8 in
>55 kW/75 HP
225 mm/10 in
525-600 V
0.37-7.5 kW 1/2-10 HP
100 mm/4 in
11-55 kW 15-75 HP
200 mm/8 in
>55 kW/75 HP
225 mm/10 in
525-690 V
all
225 mm/10 in
Table 3.1 Minimum Airflow Clearance Requirements
3.3.2 Lifting
•
Check the weight of the unit to determine a safe
lifting method
•
Ensure that the lifting device is suitable for the
task
•
If necessary, plan for a hoist, crane, or forklift with
the appropriate rating to move the unit
•
For lifting, use hoist rings on the unit, when
provided
3.3.3 Mounting
•
Mount the unit vertically
•
The drive allows side by side installation.
•
Ensure that the strength of the mounting location
will support the unit weight
•
Mount the unit to a solid flat surface or to the
optional backplate to provide cooling airflow (see
Illustration 3.2
and
Illustration 3.3
).
•
Improper mounting can result in overheating and
reduced performance.
•
Use the slotted mounting holes on the unit for
wall mounting, when provided.
Illustration 3.2 Proper Mounting with Backplate
Item A is a backplate properly installed for required airflow
to cool the unit.
Illustration 3.3 Proper Mounting with Railings
NOTE
Backplate is needed when mounted on railings.