Figure 7.5
Figure 7.6
7.5.5 Derating for Running at Low Speed
When a motor is connected to an adjustable frequency
drive, it is necessary to make sure that the cooling of the
motor is adequate.
The level of heating depends on the load on the motor as
well as the operating speed and time.
Variable (quadratic) torque applications (VT)
In VT applications such as centrifugal pumps and fans,
where the torque is proportional to the square of the
speed and the power is proportional to the cube of the
speed, there is no need for additional cooling or de-rating
of the motor.
In the graphs shown below, the typical VT curve is below
the maximum torque with de-rating and maximum torque
with forced cooling at all speeds.
Figure 7.7 Maximum load for a standard motor at 104° F [40
°
C]
driven by an AF-600 FP drive
─ ─ ─ ─
Typical torque at VT load
─•─•─•─
Max torque with forced cooling
‒‒‒‒‒
Max torque
Table 7.8
Note 1) Oversynchronous speed operation will result in the available
motor torque decreasing inversely proportional to the increase in
speed. This must be considered during the design phase to avoid
overloading the motor.
7.6 Motor
Insulation
For motor cable lengths
≤
than the maximum cable length
listed in the General Specifications tables, the following
motor insulation ratings are recommended because the
peak voltage can be up to twice the DC link voltage, 2.8
times the AC line voltage due to transmission line effects
in the motor cable. If a motor has lower insulation rating,
it is recommended to use a du/dt or sine-wave filter.
Nominal AC Line Voltage
Motor Insulation
U
N
≤
420 V
Standard U
LL
= 1300 V
420 V < U
N
≤ 500 V
Reinforced U
LL
= 1600 V
500 V < U
N
≤ 600 V
Reinforced U
LL
= 1800 V
600 V < U
N
≤ 690 V
Reinforced U
LL
= 2000 V
Table 7.9
Installation Consideration
AF-600 FP Design and Installation Guide
7-8
DET-768A
7
7
Summary of Contents for AF-600 FP Series
Page 1: ...AF 600 FPTM Fan Pump Drive Design and Installation Guide GE ...
Page 17: ...Introduction AF 600 FP Design and Installation Guide 1 10 DET 768A 1 1 ...
Page 39: ...Start Up and Functional Tes AF 600 FP Design and Installation Guide 3 6 DET 768A 3 3 ...
Page 57: ...About Programming AF 600 FP Design and Installation Guide 5 14 DET 768A 5 5 ...
Page 73: ...Application Set up Examples AF 600 FP Design and Installation Guide 6 16 DET 768A 6 6 ...
Page 83: ...Installation Consideration AF 600 FP Design and Installation Guide 7 10 DET 768A 7 7 ...
Page 87: ...Status Messages AF 600 FP Design and Installation Guide 8 4 DET 768A 8 8 ...
Page 97: ...Warnings and Alarms AF 600 FP Design and Installation Guide 9 10 DET 768A 9 9 ...
Page 101: ...Basic Troubleshooting AF 600 FP Design and Installation Guide 10 4 DET 768A 10 0 ...
Page 103: ...Terminal and Applicable Wir AF 600 FP Design and Installation Guide 11 2 DET 768A 11 1 ...