DEH40634
AN 11-1018 Rev.02, 09/26/2011
Relay 1
(E24)
Set to “9” Alarm
Relay 2
(E24)
Set to “5”Running
Electronic Overload
(F10)
Set to “4” Elec OL Trip 1
Motor Thermistor Input
(F12)
Set to “0” None
Auto-Reset (Times)
(H04)
Set to “13” Infinite Auto Reset
Drive Programming
Auto-Tune
In the event that it is desired to “auto-tune” the drive to the connected motor, reference the following
instructions along with the AF 600 FP User’s Guide (DET – 609):
With power applied to the panel –
1)
Place the Hand/Off/Auto, and Drive1/Off/Drive2 selector switches in the “Off”, and “Drive1” positions
respectively.
2)
For Full Auto tuning follow the instruction below
Quick Menu
Ok
Quick start
Ok
Once Up arrow
Ok
P-04 Auto Tuning
Ok
[1] Full Auto tune
Ok
Follow the Keypad direction
Note: If the panel has a load reactor, select “Reduced
Auto tune”.
16