Relay outputs:
Programmable relay outputs
2 Form C
Relay 01 Terminal number
1-3 (break), 1-2 (make)
Max. terminal load (AC-1)
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
240V AC, 2A
Max. terminal load (AC-15)
1)
(Inductive load @ cosφ 0.4)
240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
60V DC, 1A
Max. terminal load (DC-13)
1)
(Inductive load)
24 V DC, 0.1A
Relay 02 Terminal number
4-6 (break), 4-5 (make)
Max. terminal load (AC-1)
1)
on 4-5 (NO) (Resistive load)
2)3)
Overvoltage cat. II
400V AC, 2A
Max. terminal load (AC-15)
1)
on 4-5 (NO) (Inductive load @ cos
φ
0.4)
240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-5 (NO) (Resistive load)
80V DC, 2A
Max. terminal load (DC-13)
1)
on 4-5 (NO) (Inductive load)
24 V DC, 0.1A
Max. terminal load (AC-1)
1)
on 4-6 (NC) (Resistive load)
240V AC, 2A
Max. terminal load (AC-15)
1)
on 4-6 (NC) (Inductive load @ cos
φ
0.4)
240V AC, 0.2A
Max. terminal load (DC-1)
1)
on 4-6 (NC) (Resistive load)
50V DC, 2A
Max. terminal load (DC-13)
1)
on 4-6 (NC) (Inductive load)
24 V DC, 0.1A
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
24V DC 10mA, 24V AC 20mA
Environment according to EN 60664-1
overvoltage category III/pollution degree 2
1)
IEC 60947 part 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2)
Overvoltage Category II
3)
UL applications 300V AC2A
Cable lengths and cross-sections for control cables:
Max. motor cable length, shielded
492 ft [150 m]
Max. motor cable length, non-shielded
984 ft [300 m]
Maximum cross-section to control terminals, flexible/ rigid wire without cable end sleeves
1.5mm
2
/16 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves
1mm
2
/18 AWG
Maximum cross-section to control terminals, flexible wire with cable end sleeves with collar
0.5mm
2
/20 AWG
Minimum cross-section to control terminals
0.25mm
2
/ 24AWG
Control card performance:
Scan interval
1 ms
Control characteristics:
Resolution of output frequency at 0–1000Hz
±
0.003Hz
Repeat accuracy of
Precise start/stop
(terminals 18, 19)
≤±
0.1ms
System response time (terminals 18, 19, 27, 29, 32, 33)
≤
2ms
Speed control range (open-loop)
1:100 of synchronous speed
Speed control range (closed-loop)
1:1000 of synchronous speed
Speed accuracy (open-loop)
30–4000 rpm: error
±
8rpm
Speed accuracy (closed-loop), depending on resolution of feedback device
0–6000 rpm: error
±
0.15 rpm
Torque control accuracy (speed feedback)
max error
±
5% of rated torque
All control characteristics are based on a 4-pole asynchronous motor
Specifications
AF-650 GP Quick Guide
36
DET-759A
8
8