AF-650 GP 3-phase
Recommended fuse size
Recommended max fuse
[kW] / [HP]
0.37 / 0.5
gG-16
gG-25
0.75 / 1
1.5 / 2
2.2 / 3
3.7 / 5
5.5 / 7.5
gG-20
gG-32
7.5 / 10
11 / 15
gG-50
gG-63
15 / 20
18.5 / 25
gG-80
gG-125
22 / 30
30 / 40
37 / 50
gG-125
gG-150
45 / 60
aR-160
aR-160
55 / 75
aR-250
aR-250
75 / 100
90 / 125
gG-300
gG-300
110 / 150
gG-350
gG-350
132 / 200
gG-400
gG-400
160 / 250
gG-500
gG-500
200 / 300
gG-630
gG-630
250 / 350
aR-700
aR-700
315 / 450
aR-900
aR-900
355 / 500
400 / 550
450 / 600
aR-1600
aR-1600
500 / 650
560 / 750
aR-2000
aR-2000
630 / 900
710 / 1000
aR-2500
aR-2500
800 / 1200
Table 9.3 380–480V. IP20 / Open Chassis