Recommended max. fuse
AF-650 GP
Bussmann
Littel fuse
Ferraz-
Shawmut
Ferraz-
Shawmut
[kW] / [HP]
Type JFHR2
2)
JFHR2
JFHR2
4)
J
0.25-0.37 /
0.33-0.5
FWX-5
-
-
HSJ-6
0.75 / 1
FWX-10
-
-
HSJ-10
1.5 / 2
FWX-15
-
-
HSJ-15
2.2 / 3
FWX-20
-
-
HSJ-20
3.7 / 5
FWX-30
-
-
HSJ-30
5.5 / 7.5
FWX-50
-
-
HSJ-50
7.5 / 10
FWX-60
-
-
HSJ-60
11 / 15
FWX-80
-
-
HSJ-80
15/18.5 /
20-25
FWX-125
-
-
HSJ-125
22 / 30
FWX-150
L25S-150
A25X-150
HSJ-150
30 / 40
FWX-200
L25S-200
A25X-200
HSJ-200
37 / 50
FWX-250
L25S-250
A25X-250
HSJ-250
Table 9.10 200-240 V
1) KTS fuses from Bussmann may substitute KTN for 240 V adjustable frequency drives.
2) FWH fuses from Bussmann may substitute FWX for 240 V adjustable frequency drives.
3) A6KR fuses from FERRAZ SHAWMUT may substitute A2KR for 240 V adjustable frequency drives.
4) A50X fuses from FERRAZ SHAWMUT may substitute A25X for 240 V adjustable frequency drives.
Recommended max. fuse
AF-650
GP
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
Bussmann
[kW] /
[HP]
Type RK1
Type J
Type T
Type CC
Type CC
Type CC
0.37-0.75
/ 0.5-1
KTS-R-6
JKS-6
JJS-6
FNQ-R-6
KTK-R-6
LP-CC-6
1.5-2.2 /
2-3
KTS-R-10
JKS-10
JJS-10
FNQ-R-10
KTK-R-10
LP-CC-10
3.7 / 5
KTS-R-20
JKS-20
JJS-20
FNQ-R-20
KTK-R-20
LP-CC-20
5.5 / 7.5
KTS-R-25
JKS-25
JJS-25
FNQ-R-25
KTK-R-25
LP-CC-25
7.5 / 10
KTS-R-30
JKS-30
JJS-30
FNQ-R-30
KTK-R-30
LP-CC-30
11 / 15
KTS-R-40
JKS-40
JJS-40
-
-
-
15 / 20
KTS-R-50
JKS-50
JJS-50
-
-
-
18.5 / 25
KTS-R-60
JKS-60
JJS-60
-
-
-
22 / 30
KTS-R-80
JKS-80
JJS-80
-
-
-
30 / 40
KTS-R-100
JKS-100
JJS-100
-
-
-
37 / 50
KTS-R-125
JKS-125
JJS-125
-
-
-
45 / 60
KTS-R-150
JKS-150
JJS-150
-
-
-
55 / 75
KTS-R-200
JKS-200
JJS-200
-
-
-
75 / 100
KTS-R-250
JKS-250
JJS-250
-
-
-
Table 9.11 380–480V
Installation
AF-650 GP Quick Guide
44
DET-759A
9
9