Actual configurations vary with unit types and optional
equipment.
Illustration 3.7 Example of Motor, Line Power and Ground Wiring
3.4.4 AC Line Power Connection
•
Size wiring based upon the input current of the
drive. For maximum wire sizes, see
•
Comply with local and national electrical codes
for cable sizes.
•
Connect 3-phase AC input power wiring to
terminals L1, L2, and L3 (see
•
Depending on the configuration of the
equipment, input power will be connected to the
line power input terminals or the input
disconnect.
•
Ground the cable in accordance with grounding
instructions provided in
•
All adjustable frequency drives may be used with
an isolated input source as well as with ground
reference power lines. When supplied from an
isolated line power source (IT line or floating
delta) or TT/TN-S power line with a grounded leg
(grounded delta), set
14-50 RFI Filter
to OFF.
When off, the internal RFI filter capacitors
between the chassis and the intermediate circuit
are isolated to avoid damage to the intermediate
circuit and to reduce ground capacity currents in
accordance with IEC 61800-3.
3.4.5 Control Wiring
•
Isolate control wiring from high power
components in the adjustable frequency drive.
•
If the adjustable frequency drive is connected to
a thermistor, for PELV isolation, optional
thermistor control wiring must be reinforced/
double insulated. A 24 VDC supply voltage is
recommended.
3.4.5.1 Access
•
Remove access coverplate with a screwdriver. See
.
•
Or remove front cover by loosening attaching
screws. See
Tightening torque for front cover is 2.0Nm for
unit size 15 and 2.2Nm for unit sizes 2X and 3X.
Illustration 3.8 Control Wiring Access for IP20 / Open Chassis
Enclosures
Illustration 3.9 Control Wiring Access for IP55 / Nema 12 and
IP66 / Nema 4/4X Indoor
Installation
AF-650 GP Quick Guide
8
DET-759A
3
3