Preset ref. bit
2
1
0
Preset ref. 0
0
0
0
Preset ref. 1
0
0
1
Preset ref. 2
0
1
0
Preset ref. 3
0
1
1
Preset ref. 4
1
0
0
Preset ref. 5
1
0
1
Preset ref. 6
1
1
0
Preset ref. 7
1
1
1
Table 3.7
[19] Freeze
ref
Freezes the actual reference, which is now the
point of enable/condition for Speed up and Speed
down to be used. If Speed up/down is used, the
speed change always follows ramp 2 (
and
) in the range 0 -
[20] Freeze
output
Freezes the actual motor frequency (Hz), which is
now the point of enable/condition for Speed up
and Speed down to be used. If Speed up/down is
used, the speed change always follows ramp 2
(
and
) in the
.
NOTE
When Freeze output is active, the frequency
converter cannot be stopped via a low ‘start
[8]’ signal. Stop the frequency converter via a
terminal programmed for Coasting inverse [2]
or Coast and reset, inverse.
[21] Speed
up
Select Speed up and Speed down if digital control
of the up/down speed is desired (motor potenti-
ometer). Activate this function by selecting either
Freeze reference or Freeze output. When Speed
up/ down is activated for less than 400 msec. the
resulting reference will be increased/ decreased by
0.1 %. If Speed up/ down is activated for more
than 400 msec. the resulting reference will follow
the setting in accel/decel parameters.
Shut down
Catch up
Unchanged speed
0
0
Reduced by %-value
1
0
Increased by %-value
0
1
Reduced by %-value
1
1
Table 3.8
[22] Speed down
Same as Speed up [21].
[23] Set-up select
bit 0
Select Set-up select bit 0 or Select Set-up
select bit 1 to select one of the four set-ups.
Set
to Multi Set-up.
[24] Set-up select
bit 1
Same as Set-up select bit 0 [23].
[26] Precise stop
inv.
Prolongs stop signal to give a precise stop
independent of speed.
Sends an inverted stop signal when the
precise stop function is activated in
.
Precise stop inverse function is available for
terminals 18 or 19.
[27] Precise start,
stop
Use when Precise ramp stop [0] is selected in
.
Illustration 3.15
[28] Catch up
Increases reference value by percentage
(relative) set in
[29] Slow down
Reduces reference value by percentage
(relative) set in
[30] Counter
input
Precise stop function in
acts as Counter stop or speed
compensated counter stop with or without
reset. The counter value must be set in
H-84 Precise Stop Counter Value
.
[32] Pulse input
Use pulse sequence as either reference or
feedback. Scaling is done in parameter group
group E-6#.
[34] Ramp bit 0
Enables a choice between one of the 4 ramps
available, according to the table below.
[35] Ramp bit 1
Same as Ramp bit 0.
Preset ramp bit
1
0
Ramp 1
0
0
Ramp 2
0
1
Ramp 3
1
0
Ramp 4
1
1
Table 3.9
Parameter Descriptions
AF-650 GP Programming Guide
44
DET-618C
3