3.10.2 O-1# Control Settings
Parameters to configure the option control word profile.
O-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid
for the fieldbus installed in slot A will be visible in the keypad
display.
For guidelines in selection of
GE Drive profile
and
[1] PROFIdrive
profile
refer to the
design guide
of the related product.
For additional guidelines in the selection of
[1] PROFIdrive profile
and
[5] ODVA
, see
Operating Instructions
for the installed
fieldbus.
Option:
Function:
[0]
*
Drive Profile
[1]
PROFIdrive profile
[5]
ODVA
O-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of bits
12–15 in the status word.
[0]
No function
[1]
*
Profile Default Function corresponds to the profile default
selected in
O-10 Control Word Profile
.
O-14 Configurable Control Word CTW
Option:
Function:
Selection of control word bit 10 if it is active
low or active high.
[0]
None
[1]
*
Profile
default
[2]
CTW Valid,
active low
[4]
PID error
inverse
When enabled, it inverts the resulting error
from the process PID controller. Available
only if "Configuration Mode" is set to
"Surface Winder", "Extended PID Speed OL"
or "Extended PID Speed CL".
[5]
PID reset I
part
When enabled, resets the I-part of the
Process PID controller. Equivalent to
PI-40 Process PID I-part Reset
. Available only if
"Configuration Mode" is set to "Surface
Winder", "Extended PID Speed OL" or
"Extended PID Speed CL".
[6]
PID enable
When enabled, enables the extended process
. Available only if "Configuration
Mode" is set "Extended PID Speed OL" or
"Extended PID Speed CL".
3.10.3 O-3# Drive Port Settings
Parameters to configure the GE drive port.
O-30 Protocol
Option:
Function:
[0]
Drive
Communication according to the Drive
Protocol.
[1]
Drive MC
Select the protocol for the drive (standard)
port.
[2]
*
Modbus RTU
O-31 Address
Range:
Function:
1
*
[1 - 255]
Enter the address for the Drive (standard) port.
Valid range: 1-126.
O-32 Drive Port Baud Rate
Option:
Function:
[0]
2400 Baud
Baud rate selection for the Drive (standard)
port.
[1]
4800 Baud
[2]
*
9600 Baud
[3]
19200 Baud
[4]
38400 Baud
[5]
57600 Baud
[6]
76800 Baud
[7]
115200 Baud
O-33 Drive Port Parity
Option:
Function:
Parity and Stop Bits for the protocol
O-30 Protocol
using the Drive Port.
For some of the protocols, not all
options are visible. Default depends
on the protocol selected.
[0]
*
Even Parity, 1 Stop Bit
[1]
Odd Parity, 1 Stop Bit
[2]
No Parity, 1 Stop Bit
[3]
No Parity, 2 Stop Bits
O-34 Estimated cycle time
Range:
Function:
0 ms
*
[0 - 1000000
ms]
In noisy environments, the interface may
be blocked by due to overload of bad
frames. This parameter specifies the time
between two consecutive frames on the
network. If the interface does not detect
valid frames in that time it flushes the
receive buffer.
Parameter Descriptions
AF-650 GP Programming Guide
88
DET-618C
3