3.12 PB-##
Profibus
Parameter group related to Field Installed Profibus DP
Network Communications Option Module.
PB-00 Setpoint
Range:
Function:
0
*
[0 - 65535] This parameter receives cyclical reference from a
Master Class 2. If the control priority is set to
Master Class 2, the reference for the frequency
converter is taken from this parameter, whereas
the cyclical reference will be ignored.
PB-07 Actual Value
Range:
Function:
0
*
[0 - 65535] This parameter delivers the MAV for a Master
Class 2. The parameter is valid if the control
priority is set to Master Class 2.
PB-15 PCD Write Configuration
Array [10]
Option:
Function:
Select the parameters to
be assigned to PCD 3 to
10 of the messages. The
number of available PCDs
depends on the message
type. The values in PCD 3
to 10 will then be written
to the selected
parameters as data
values. Alternatively,
specify a standard
Profibus message in
[0]
*
None
[7]
Accel Time 1
[8]
Decel Time 1
[15]
Motor Speed High Limit [Hz]
[16]
Motor Speed Low Limit [Hz]
[17]
Motor Speed High Limit [RPM]
[18]
Motor Speed Low Limit [RPM]
[40]
Torque Limiter (Driving)
[41]
Torque Limiter (Braking)
[52]
Minimum Reference
[53]
Maximum Reference
[62]
Catch up/slow Down Value
[110]
Accel Time 2
[111]
Decel Time 2
[190]
Digital & Relay Bus Control
[193]
Pulse Out #27 Bus Control
[195]
Pulse Out #29 Bus Control
[197]
Pulse Out #X30/6 Bus Control
[222]
Jog Accel/Decel Time
[223]
Quick Stop Decel Time
PB-15 PCD Write Configuration
Array [10]
Option:
Function:
[653]
Terminal 42 Output Bus
Control
[663]
Terminal X30/8 Bus Control
[748]
PCD Feed Forward
[890]
Bus Jog 1 Speed
[891]
Bus Jog 2 Speed
[1280] Fieldbus CTW 1
[1282] Fieldbus REF 1
PB-16 PCD Read Configuration
[10] Array
Option:
Function:
Select the parameters to be
assigned to PCD 3 to 10 of
the messages. The number
of available PCDs depends
on the message type. PCDs
3 to 10 contain the actual
data values of the selected
parameters. For standard
.
[0]
*
None
[515]
Readout: actual setup
[1200] Control Word
[1201] Reference [Unit]
[1202] Reference %
[1203] Status Word
[1205] Main Actual Value [%]
[1209] Custom Readout
[1210] Power [kW]
[1211] Power [hp]
[1212] Motor Voltage
[1213] Frequency
[1214] Motor current
[1215] Frequency [%]
[1216] Torque [Nm]
[1217] Speed [RPM]
[1218] Motor Thermal
[1219] KTY sensor temperature
[1220] Motor Angle
[1221] Torque [%] High Res.
[1222] Torque [%]
[1225] Torque [Nm] High
[1230] DC Link Voltage
[1232] Brake Energy /s
[1233] Brake Energy /2 min
[1234] Heatsink Temp.
[1235] Drive Thermal
[1238] Logic Controller State
[1239] Control Card Temp.
Parameter Descriptions
AF-650 GP Programming Guide
DET-618C
97
3
3