7 Protection Parameter Settings
P50 Agile P153
7-10
P153/EN M/B
2.10
DISTURBANCE RECORD Settings
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to zzzz
This setting specifies to enter the set password
2.
Trigger Position
50%
10% to 90% step 1%
This setting sets the trigger point as a percentage of the duration. For example, the default setting, which is set to 50% (of 1.0s) gives 0.5s
prefault and 0.5s post fault recording times.
2.11
COMMISSION TEST Settings
Sr. No
Parameter
Defaults setting
Setting / Ranges
1.
Password
0000
0000 to zzzz
This setting specifies to enter the set password
2.
Test Mode
Disabled
Disabled, Test Mode, Contacts Blocked
This setting allows secondary injection testing to be performed on the relay itself.
3.
Test Pattern
000000
0 = not operated , 1 = operated
This setting is used to select the output relay contacts that will be tested when the Contact Test cell is set to Apply Test.
4.
Contact Test
No Operation
No Operation, Apply Test, Remove Test
This setting is used to test the relay output contact operation.
5.
Test LEDs
No Operation
No Operation / Apply Test
This setting is used to test the 2 no’s programmable LED’s.
2.12
GROUP Settings
The following settings are common to GROUP 1 and 2.
2.12.1
SYSTEM CONFIG SETTINGS
Sr. No
Parameter
Default setting
Setting Range
1.
2nd Harmonic
Disabled
Enabled / Disabled
This setting is used to enable or disable the 2nd Harmonic blocking of the overcurrent protection.
2.
2ndHarm Thresh
20%
5% to 70% step 1%
This setting is used to specify the 2nd Harm Threshold value. If the level of 2nd harmonic/fundamental in any phase current or neutral
current exceeds the setting, the overcurrent protection will be blocked as selected.
3.
I>lift 2H
10.00*In
4 to 32*In step 0.01*In
The 2nd harmonic blocking is applied only when the fundamental current is above 2nd Harm Thresh and below I> lift setting. The reset
levels are 95% of these thresholds.
2.12.2
OVERCURRENT Settings
2.12.2.1
I>1 Function
Sr. No
Parameter
Default setting
Setting Range
1.
I>1 Function
IEC S Inverse
Disabled / DT / IEC S Inverse / S Inverse
(1.3Sec) / IEC V Inverse / IEC E Inverse / UK
LT Inverse / IEEE M Inverse / IEEE V Inverse
/ IEEE E Inverse / US Inverse / US ST
Inverse
This setting determines the tripping characteristic for the first stage overcurrent element.
Summary of Contents for Agile P50 Series
Page 3: ...P50 Agile P153 1 Introduction P153 EN M B 1 1 INTRODUCTION CHAPTER 1...
Page 4: ...1 Introduction P50 Agile P153 1 2 P153 EN M B...
Page 10: ...1 Introduction P50 Agile P153 1 8 P153 EN M B...
Page 11: ...P50 Agile P153 2 Safety Information P153 EN M A 2 1 SAFETY INFORMATION CHAPTER 2...
Page 22: ...Chapter 2 Safety Information P50 Agile P153 2 12 P153 EN M A...
Page 23: ...P50 Agile P153 3 Hardware Design P153 EN M B 3 1 HARDWARE DESIGN CHAPTER 3...
Page 24: ...3 Hardware Design P50 Agile P153 3 2 P153 EN M B...
Page 32: ...3 Hardware Design P50 Agile P153 3 10 P153 EN M B...
Page 33: ...P50 Agile P153 4 Front Panel P153 EN M B 4 1 FRONT PANEL CHAPTER 4...
Page 34: ...4 Front Panel P50 Agile P153 4 2 P153 EN M B...
Page 39: ...P50 Agile P153 5 Configuration P153 EN M B 5 1 CONFIGURATION CHAPTER 5...
Page 40: ...P50 Agile P153 5 Configuration P153 EN M B 5 2...
Page 150: ...P50 Agile P153 5 Configuration P153 EN M B 5 112...
Page 151: ...P50 Agile P153 6 Protection Functions P153 EN M B 6 1 PROTECTION FUNCTIONS CHAPTER 6...
Page 152: ...6 Protection Functions P50 Agile P153 6 2 P153 EN M B...
Page 168: ...7 Protection Parameter Settings P50 Agile P153 7 2 P153 EN M B...
Page 189: ...P50 Agile P153 8 Monitoring Control P153 EN M B 8 1 MONITORING CONTROL CHAPTER 8...
Page 190: ...8 Monitoring Control P50 Agile P153 8 2 P153 EN M B...
Page 207: ...P50 Agile P153 9 SCADA Communications P153 EN M B 9 1 SCADA COMMUNICATIONS CHAPTER 9...
Page 208: ...12 SCADA Communications P50 Agile P153 9 2 P153 EN M B...
Page 220: ...12 SCADA Communications P50 Agile P153 9 14 P153 EN M B...
Page 221: ...P50 Agile P153 10 Installation P153 EN M B 10 1 INSTALLATION CHAPTER 10...
Page 222: ...10 Installation P50 Agile P153 10 2 P153 EN M B...
Page 234: ...13 Commissioning Instructions P50 Agile P153 13 2 P153 EN M B...
Page 242: ...12 Maintenance and Troubleshooting P50 Agile P153 12 2 P153 EN M B...
Page 250: ...12 Maintenance and Troubleshooting P50 Agile P153 12 10 P153 EN M B...
Page 252: ...13 Technical Specifications P50 Agile P153 13 2 P153 EN M B...
Page 263: ...P50 Agile P153 14 Wiring Diagrams P153 EN M B 14 1 WIRING DIAGRAMS CHAPTER 14...
Page 264: ...14 Wiring Diagrams P50 Agile P153 14 2 P153 EN M B...
Page 267: ......