13
Accessories
Auxiliary Switch
–
Field installable kit available
(Breaker accessory)
The auxiliary switch is used for indication of breaker main
contact position. It is available on manually and electrically
operated breakers in either a 4-stage or 7-stage configura-
tion. The 4-stage switch yields 3NO and 3NC contacts while
the 7-stage switch yields 6NO and 6NC contacts. Normally
open (NO) contacts follow the breaker primary contact posi-
tion while normally closed (NC) contacts operate opposite
the breaker primary contacts. All auxiliary switch contacts
feature rugged double-break construction. Refer to breaker
wiring diagram 10057403P1 for contact configurations and
secondary disconnect terminations. Ratings of the auxiliary
switch contacts are shown in Table 13.1.
Table 13.1
Auxiliary switch ratings and contact operation
Table 13.2
Table 13.3
Bell Alarm with/without Lockout
–
Field installable kit available
(Breaker accessory)
The bell alarm device is provided with two C-form contacts —
each C-form contact is 1NO and 1NC contact with a common
connection. The bell alarm device operates whenever the
breaker trips due to a protective function of the trip unit. It
can be used to provide remote indication of a fault trip
and/or disable electrical operation of breakers that may
have automatic control.
For Power+
™
and MicroVersaTrip Plus
™
trip units, the bell
alarm will operate for overload, short circuit and ground
fault trips. For MicroVersaTrip PM
™
trip units, the bell alarm
will operate for the same overcurrent trips plus any of the
protective relay trips that are enabled in the trip unit.
Tripping via the manual trip button, shunt trip, undervoltage
device or open fuse lockout will not operate the bell alarm.
The bell alarm can be furnished with a mechanical lockout
feature that will prevent the breaker from being manually
closed until the lockout is reset. Reset of the contacts and
lockout feature is accomplished by pushing the yellow “reset”
button on the breakerescutcheon. The reset button also serves
as a target indicator that the bell alarm has been operated.
Ratings of the bell alarm contacts are shown in Table 13.4
Table 13.4
Bell alarm contact ratings
Table 13.5
Electrical Lockout
– Field installable kit available
(Breaker accessory)
The electrical lockout device provides a means to electrically
enable or disable manual closing of a circuit breaker. This
device must be energized prior to attempting to manually
close the breaker. Once the breaker is closed, loss of voltage
will not trip the breaker. A manual bypass interlock is provided
for initial startup. Refer to the undervoltage device for ratings
and coil characteristics. (Note: Interlocking of electrically oper-
ated breakers does not require an electrical lockout device.)
Table 13.6
Fuse and Fan
– WP-50
(Breaker accessory)
The WP-50 breaker is provided with integrally mounted cooling
fans. Fan control is initiated by the trip unit which signals a fan
controller to turn the fans on and off when the load current
exceeds or drops below 4200 amperes. The fan motors require
120Vac and the fan controller requires 24Vdc auxiliary power.
Both the fans and the fan controller are wired to the breaker
secondary disconnect. The 24Vdc source can be the POWER
LEADER
™
power supply used for MicroVersaTrip PM
™
trip
units. 120Vac is normally provided by the switchgear control
power transformer. Power requirement for each fan is
0.2amps @ 120Vac (two fans installed).
Fuse Roll-out
– Fuse carriage
(Equipment accessory)
A fuse roll-out is used in conjunction with breakers that do
not have integral fusing and are applied in high available
short circuit current systems. The fuse roll-out is equipped
with wiring and a secondary disconnect for blown fuse
sensing. The sensing wiring is connected to the breaker-
mounted Open Fuse Lockout (OFLO). The OFLO will trip the
circuit breaker whenever a fuse in the roll-out opens due to
short circuit interruption. Note that the WavePro breaker
Field installable electrical lockout kit catalog numbers
Control voltage
WP-08 / 16 / 20
WP-32 / 40 / 50
120Vac 50/60Hz
WPELSF56120
WPELLF56120
240 Vac 50/60Hz
WPELSF56240
WPELLF56240
24Vdc
WPELSFDC024
WPELLFDC024
48Vdc
WPELSFDC048
WPELLFDC048
110Vdc
WPELSFDC110
WPELLFDC110
125Vdc
WPELSFDC125
WPELLFDC125
250Vdc
WPELSFDC250
WPELLFDC250
Field Installable Bell Alarm Kit Catalog Numbers
(kit provides choice of with or without lockout)
WP-08 / 16 / 20
WP-32 / 40 / 50
WPBASF
WPBALF
Bell Alarm Contact Ratings
AC Ratings
DC Ratings
6A @ 240Vac
0.5A @ 125Vdc
0.25A @ 250Vdc
Field installable auxiliary switch kit catalog numbers
Auxiliary switch
WP-08 / 16 / 20
WP-32 / 40
WP-50
Four stage
WPAUXSF4STG
WPAUXLF4STG
WPAUXXF4STG
Seven stage
WPAUXSF7STG
WPAUXLF7STG
WPAUXXF7STG
Auxiliary switch contact operation
Breaker primary contacts
“a”-contact (NO)
“b”-contact (NC)
Open or tripped
Open
Closed
Closed
Closed
Open
Auxiliary Switch Ratings
¬
Rating (Amperes)
Control Voltage
Non-inductive
Inductive
24
15
10
DC
125
10
5
250
5
5
AC - 60Hz
120
15
15
240
10
10
¬
20A continuous rating of switch limited to 15A continuous rating of #16AWG
wire on drawout breakers