TABLE 1 1 TRIP FUNCTIONS AVAILABLE
Features
BASIC FUNCTIONS
ADD TO BASIC FUNCTIONS
•
Adjustable Current Setting
•
Adj Long-Time Pickup
LONG
•
Adj Long-Time Delay
TIME
•
Time
•
Remote Long-Time Timing Light
•
Adj Short-Time Pickup
SHORT
•
Short-Time
TIME
•
Short-Time l2t Switch
INSTANT A-
•
Instantaneous
NEOUS
•
Adj High Range Instantaneous
•
Adj Ground Fault Pickup
GROUND
-1
PH, 2.W-3PH, 3/4
-
W
FAULT
-Ground Re_turn.
•
Adj Ground Fault Delay
•
Trip Indication Targets
-Overload
&
Short Circuit
OTHER
-local only
FUNCTIONS
-local and remote
-0/L, S/C and Ground Fault
-local only(2)
-local and remote
•
Zone Selective Interlock
-Ground Fault<3)
-Short Time<D
1 Short-Time Delay is required
2 Standard when Ground Fault specified
3 Ground Fault required
STD.-or-5-or-H-or-M
L
T
G-or-GR A 1 -or-A2-or-A3-or-A
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
TABLE
1 2
M ICROVERSATRI Pr"' TRIP C HARACTERISTICS
Current
Setting
(X)
(X)
(Multiple
Pickup
Fixed
Tapped of Sensor (Multiple
Delay
Maximum Sensors
Sensors
Current of Current
<D
Frame
Rating
Rating)
Rating) (Seconds)
Size
(Amps)
Sensor
Rating
(X)
(C)
1 00, 1 50,
1 00, 150,
225, 300
.5, .6, .7,
.8, .9,
2.5, 5,
AKR-30
800
225, 300,
or
.8, .85, .9, 1 .0, 1 . 1
10, 21
400, 600,
300, 400
95, 1 .0
(C)
800
600, 800
(X)
300, 400,
300, 400,
600, 800
AKR-50
1 600
600, 800
or
"
"
"
1 200, 1 600 600, 800
1 200, 1 600
800, 1200, 800, 1 200
AKRT-50
2000
1 600, 2000 1 600, 2000
"
"
"
1 200, 1 600, 1200, 1 600
AKR-75
3200
2000, 3200 2000, 3200
"
"
"
1 600, 2000, 1 600, 2000
AKR-1 00
4000
3000, 4000 3000, 4000
"
"
"
1 Time delay shown at 600% of ampere setting at lower limit of each baRd.
2 Time delay shown at lower limit of each band.
All pickup tolerances are
±
1 0%
Ground Fault pickup not to exceed 1 200 amperes.
Short-time
Adjustable
Instantaneous
Pickup
Pickup
Short-time
(Multiple
Delay
(Multiple
l't
of Current
®
of Sensor
<D
Rating) (Seconds)
Rating)
(Seconds)
(C)
(X)
1 .5, 2, 2.5,
0.10,
1 .5, 2, 2.5,
3, 4, 5, 7,
0.22,
3, 4, 6, 8,
0.4
9
(C)
0.36
10 (X)
"
"
"
"
"
"
"
"
"
"
1 .5, 2, 2.5, 3,
"
"
4, 5, 7, 9 (X)
"
Z1 -or-Z2-or-Z
X
X
X
X
Ground Fault
Pickup
(Multiple
of Sensor
Delay
Current
®
Rating)
(Seconds)
(X)
.2, .25, .3, 0. 1 0, 0.22,
.35, .4, .45,
0.36
.5, .6 (X)
"
"
"
"
.2, .22, .24,
.26, .28, .30,
"
.34, .37 (X)
.2, .22, .24,
.26, .28, .3 (X)
C
�
current
setting
X
�
sensor
current
6 1
www
. ElectricalPartManuals